If the adjustment ranges are exceeded, the message "Outside
parameter limits
" appears. The editing procedure can be aborted with
[ESC]

or the displayed limit value can be accepted with [OK].

This function enables reading out parameter adjustment data as well
as writing parameter adjustment data into the sensor via the indicating
and adjustment module. A description of the function is available in the
operating instructions manual "Indicating and adjustment module".

The following data are read out or written with this function:

l

Measured value presentation

l

Adjustment

l

Damping

l

Linearisation curve

l

Sensor-TAG

l

Displayed value

l

Display unit

l

Scaling

l

Current output

l

Unit of measurement

l

Language

The following safety-relevant data are not read out or written:

l

SIL

l

HART mode

l

PIN

l

Application

Copy sensor data

Copy sensor data?

Basic adjustment
If the "Reset" (sensor-specific basic adjustment) is carried out, the
sensor resets the values of the following menu items to the reset
values (see chart):

Menu section

Function

Reset value

Basic settings

Unit of measurement

bar

Temperature unit

°C

Zero/Min. adjustment

Measuring range begin

Span/Max. adjustment

Measuring range end

Density

1 kg/l

Density unit

kg/l

Damping

1 s

Linearisation

linear

Copy sensor data

Reset

28

Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor • 4 … 20 mA