Commissioning, operation – WIKA AC-1 User Manual

Page 19

background image

19

WIKA operating instructions pressure transmitter model AC-1

14026285.01 11/2012 GB/D/F/E

GB

Humidity can affect the operating characteristics of

electronic components and sensors, thus a good

positioning prevents problems and extends the

service life. Electronic components and sensors can

be adversely affected due to temperature changes in

combination with condensing humidity (e.g. in evapo-

rators with de-icing systems).

Although the ingress protection of the pressure

transmitter is IP 67 or IP 6K9K, this is not hermetically

sealed. Under critical conditions, there is the danger

that small air volumes can penetrate or diffuse

through the case. Thus, over time, humidity can

collect in the sensor and cause measuring errors.

It is therefore recommended that the pressure trans-

mitter is placed in a location with low humidity and

temperature fluctuations. For chill cabinets or cold

rooms, this place is on the inlet pipe on the outside of

the main cooling chamber, e.g. below the chill cabinet

where the piping comes out of the chill cabinet.

If positioning is required closer to the evaporator, it is

recommended that a capillary is used between the

evaporator outlet line and the pressure transmitter.

6. Commissioning, operation

Pressure transmitter with capillary

(exterior view)

Pressure transmitter with capillary

(cross-section)