WIKA operating instructions pressure transmitter model AC-1

14026285.01 11/2012 GB/D/F/E

GB

3.6 Operating conditions
Ingress protection (per IEC 60529)

The ingress protection depends on the type of electrical connection.

Circular connector M12 x 1: IP 67

Metri-Pack series 150:

IP 67

Cable outlet:

IP 69K

The stated ingress protection only applies when plugged in using mating connectors that have the

appropriate ingress protection.

Temperatures

Medium: -40 ... +100 °C

-40 ... +212 °F

Ambient: -25 ... +85 °C

-13 ... +185 °F

Storage: -25 ... +85 °C

-13 ... +185 °F

Resistance

The pressure transmitter is resistant to the refrigerants R12, R22, R134a, R404a, R407c, R410a, R502,

R507.

Resistance to further refrigerants on request.

3.7 Electrical connections
Short-circuit resistance

S

+

vs. 0V

Reverse polarity protection

U

B

vs. 0V