beautypg.com

M&G DuraVent DuraStack® User Manual

Page 31

background image

31

Figure 51

Figure 52

Figure 53

Figure 54

Figure 55

Figure 56

VarIaBLE LEngtH

1. The variable length (LV) is used only to
make odd lengths, it doesn’t compensate
thermal expansion. See Figure 65 for typical
location.

2. The variable length assembly includes a
sliding flanged female coupling, a flanged
retaining band, a locking band, a insulation
band and split outer casing. Inner flue sealant
S-2000 or S-650 is necessary depending on
the flue gaz temperature.

3. Installation steps :

a. Measure the distance required for the
variable length. See Figure 58.

b. Cut the inner wall at the dimension
found at point ‘a.’ plus 1”. Cut the split outer
casing at dimension plus 5/8”. Then cut the
insulation band at dimension (DIS only). See

Figure 59.

c. Install the interior assembly between the
two parts. Put one bead of sealant between
the couplings flanges as a regular length
installation. See Figure 60.

Desired Length

Desired Length

Move Outer Casing

Supplied Tool

Wrench