M&G DuraVent DuraStack® User Manual
Page 12

12
4. When using guy wire, the cable must 
be slightly slack or loose to allow thermal 
expansion.
5. When using rigid bracing, the maximum 
vertical height between supports must 
be reduced to 5’ to compensate thermal 
expansion.
tErmInatIon HEIgHt
Chimneys and vents shall terminate above 
the roof level in accordance with the 
following requirements:
1. Five feet above the roof level or any 
adjacent flat roof, wall parapet or air intakes, 
and/or in accordance with the following 
NFPA 211 requirements.
2. Where chimney terminates at less than 10
Figure 8
feet from any adjacent ridge, wall or parapet, 
the chimney shall terminate at minimum of 3
feet above the ridge, wall, or parapet.
3. Where chimney terminates at more than 10 
feet from ridge, wall, or parapet, a minimum 
height of 2 feet shall be required above the 
ridge wall or parapet.
muLtI-EngInE EXHauSt SyStEmS
A common exhaust system for multiple 
engine or turbine installations is generally 
not recommended. A separate exhaust 
system should be provided for each engine 
or turbine. Check with your engine or turbine 
manufacturer prior to common exhaust
system design. Exhaust gas from operating 
units tends to flow to non-operating units 
where condensation may form. 
Important
Water in engine or turbines at start-up 
may cause damage. In general, a separate 
exhaust system should be provided for 
each engine or turbine.
SECtIon B- tEES, ELBoWS, InCrEaSErS
90° tEE (t90)
1. Generally used to connect the horizontal 
length from the appliance to the vertical 
length when clean-outs access or drain is 
required.
2. 90° should not be used for changing flow 
direction in diesel or turbine exhaust.
3. For supporting the tee, the preferred 
location is above the tee (see Figure 9).
4. If it is not possible to suspend the tee, it 
may be supported from the base (see Figure 
10). When this is necessary, a short length 
should be installed between the tee and the 
tee cap or Drain-Tee Cap for a good clean-out 
or inspection access.
Important
Cables and roof anchors designed for 30 lb. 
per sq. ft. force on chimney projected area.
See Table 7 for "H" dimensions
Maximum
Height
- See
Table 6
H
H
Guy Cable * tensioners
and roof anchors * (by
others)
Support
Expansion
Length
Guide
Support
Brace
5' Max
