beautypg.com

DuraVent DuraTech 10-24 Installation User Manual

Page 11

background image

11

9. Install Attic Insulation Shield: Install

the Attic Insulation Shield where the chimney

passes into an attic. It’s purpose is to prevent

debris and building insulation from getting too

close to the chimney (Fig 10). An installed

Attic Insulation Shield is 15 inches high. In

attic areas where this shield cannot fit, you

must enclose the attic portion of the chimney

in a framed enclosure. If the chimney is fully

enclosed through the attic, an Attic Insulation

Shield is not required. Where the chimney

passes into the attic, install the Attic Insulation

Shield as follows:

a. If the Firestop Radiation Shield extends

above the attic floor, no modifications are

necessary. The Firestop Radiation Shield will

fit inside the Attic Insulation Shield.

b. Assemble Chimney Sections until at least

18 inches of chimney extends above the

Firestop Radiation Shield.

c. Slip the Attic Insulation Shield over the

Chimney and Firestop Radiation Shield until

the base sits squarely on the framed opening

(Fig 6 & 10).

d. Secure the Attic Insulation Shield to the

top of the framed opening using at least (3)

8-penny nails or (3) #8, 1-1/2” wood screws

per side (Fig 10).

e. Wrap the Collar of the Attic Insulation

Shield around the chimney and fasten it

loosely. Slide the Collar down to meet the Attic

Insulation Shield. Tighten the bolts to secure

the Collar in place (Fig 11).

10. Attach Flashing: In new construction,

assemble the Chimney Sections to a point

above the roof, then slip the Flashing over

the chimney. On an existing roof, center

and install the Flashing before extending the

chimney above the roof. Allow space to permit

sliding the next Chimney Section up through

the Flashing. Always ensure the chimney

Figure 11

remains vertical (use a level), and that at least

a 2-inch clearance to combustible materials is

maintained all around. Install the upper edge

of the Flashing under the roofing. Nail to the

roof along the upper edge and down each

side with 1-inch roofing nails. Do not nail the

lower edge of the Flashing (Fig 12). Be sure

to follow local building practices, as needed.

Seal all nail heads with a non-hardening

waterproof sealant. On flat or tarred and

graveled roofs, nail and seal the Flat Roof

Flashing to the roof on all sides with roofing

compound. Do not put screws through the

Flashing into the Chimney Pipe.

11. Finish Top: Apply a non-hardening

waterproof sealant around the chimney at the

point where the Storm Collar will meet the

chimney just above the Flashing, and also

along the vertical seam of the chimney pipe,

where it is exposed to the weather (Figures

12 and 13). Slide the Storm Collar down

over the chimney to the top of the Flashing.

Tighten the bolts of the Storm Collar and seal

the Storm Collar against the sealant. After

installing sufficient Chimney Sections to meet

the height requirement as shown in Figure

1, attach the Chimney Cap onto the top of