beautypg.com

Components, Function, Specification – Dow Protected Membrane Roof EN User Manual

Page 14: General

background image

®™Trademark of The Dow Chemical Company (“Dow”) or an affiliated company of Dow

C

O

M

P

O

N

E

N

T

S

A

l

l

O

t

h

e

r

C

o

m

p

o

n

e

n

t

s

1 4

Function

The

roof deck

should:

• Provide structural support to

accommodate both live and
dead loads without significant
deflection.

• Provide dimensional stability by

forming a stable substrate not
affected adversely by cyclical
thermal- and moisture-induced
movement.

• Provide fire resistance as deter-

mined by the building type
and intended use.

• Provide a substrate for the roof

system.

• Accommodate building move-

ment. Where necessary, building
expansion joints and roof area
dividers should be designed
and installed.

• Provide for drainage (either by

sloping the roof deck or using
tapered insulation or both).
The roof surface should be
sound and should drain water
freely within 48 hours follow-
ing a rain. Every effort should
be made to isolate and correct
the causes of any standing
water or ponding on the roof.
CRCA recommends a minimum
slope of 1/4" (6 mm) per foot
(2 percent). However, if the roof
is designed to allow ponding,
ensure the insulation is not
adhered to the membrane
and a filter fabric is used.

• Provide suitable roof drains

and gutters. Care should be
taken to prevent ballast from
entering the drains and/or
gutters by using perforated
collars or paving stones.
When concerns exist, a
drainage assessment should
be conducted per Sheet Metal
and Air Conditioning
Contractors’ National
Association guidelines.

The

membrane

should:

• Provide a continuous water-

proofing barrier to protect the
interior environment.

• If the membrane is tacky, use

a slip or separation sheet (e.g.,
4-mil polyethylene) to mini-
mize adhesion between the
membrane and insulation.

• If there are compatibility issues

with the membrane, such as
with certain PVC or coal tar
membranes, refer to the
manufacturer’s or supplier’s
recommendations. In some
cases, a slip or separation sheet
(e.g., 4-mil polyethylene) may
be required.

The

flashing

should:

• Provide a continuous water-

proofing barrier when tied
into the membrane to protect
the interior environment.

• Extend well above the expected

high water level (typically 8"
[200 mm] minimum).

Specification

General:

The overall system

(including membrane and insu-
lation) should be designed so that
the dew point is located above
the membrane. The system should
be designed so that freezing will
not occur at the membrane level.

Where required, an adequate

thermal barrier should be pro-
vided between the insulation and
the interior of the building. The
thermal barrier may consist of the
deck, a ceiling assembly or an
underlayment board equivalent
to 1/2" (13 mm) gypsum board.

Membrane:

Refer to membrane

manufacturer’s literature for
details. The manufacturer or
supplier of the membrane shall
be responsible for determining
compatibility of the membrane
with STYROFOAM

Brand

Extruded Polystyrene Foam
Insulation.

Roof deck and flashing:

Refer

to general roofing specification
for details.

Installation Notes

See the CRCA Roofing

Specification Manual. Details
available at: http://www.roofing
canada.com/ItemsForSale.asp

Components

A L L

O T H E R

C O M P O N E N T S