Group 4 : motor control parameter set (level 2), Group 5 : fieldbus communications (level 2) – Beijer Electronics AN-BEI-H2-038 User Manual
Page 9

APPLICATION NOTE AN‐BEI‐H2‐038
Date: 15/02/12
AN‐BEI‐H2‐038 Modbus RTU Control and Register Mapping
9
Group 3 : User PID control (Level 2)
Parameters
Register
Number
Description
Range
Scaling
Type
P3‐01
301
User PID Proportional Gain
1 to 300
1 = 0.1
U16
P3‐02
302
User PID Integral time constant
0 to 300
1 = 0.1
U16
P3‐03
303
User PID Differential time constant
0 to 100
1 = 0.01
U16
P3‐04
304
User PID operating mode
0: Direct
1: Inverse
U16
P3‐05
305
User PID reference select
0: Digital preset (P3‐06)
1: 1
st
Analog input
2: 2
nd
Analog input
U16
P3‐06
306
User PID digital reference
0 to 1000
1 = 0.1%
U16
P3‐07
307
User PID controller output high limit
P3‐08 to 1000
1 = 0.1%
U16
P3‐08
308
User PID controller output low limit
0 to P3‐07
1 = 0.1%
U16
P3‐09
309
User PID output control
0: Digital output limits
1: 1
st
Analog variable upper limit
2: 1
st
Analog variable lower limit
3: PID output + 1
st
analog input
U16
P3‐10
310
User PID feedback select
0: 2
nd
Analog input
1: 1
st
Analog input
U16
P3‐11
311
PID error to enable ramps
0 to 250
1 = 0.1%
U16
P3‐12
312
PID feedback value display scaling factor
0 to 50000
0: Disabled
1 = 0.001
U16
P3‐13
313
PID feedback wake‐up level
0 to 1000
1 = 0.1%
U16
P3‐14
314
Standby Active Speed
0 to 7200 (Limited by P1‐01)
3000 = 50.0Hz
U16
Group 4 : Motor control parameter set (Level 2)
Par
Register
Number
Description
Range
Scaling
Type
P4‐02
402
Motor parameter
auto‐tune
0: Disable
1: Enable
U16
Group 5 : Fieldbus communications (Level 2)
Par
Register
Description
Range
Scaling
Type
P5‐01
501
Fieldbus drive address
0…63
1 = 1
U16
P5‐03
503
Modbus baudrate
0 = 9.6kbps,
1 = 19.2kpbs,
2 = 38.4kpbs,
3 = 57.6kpbs,
4 = 115 kbps
U16
P5‐04
504
Modbus data format
0 = N‐1 : No Parity 1 stop bit
1 = N‐2 : No parity 2 stop bits
2 = O‐1 : Odd parity 1 stop bit
3 = E‐1 : Even parity 1 stop bit
U16
P5‐05
505
Comms loss timeout
0...0.1... 5.0
1 = 0.1s
U16
P5‐06
506
Communications loss action
0: Trip
1: Ramp to Stop then trip
2: Ramp to stop (No trip)
3: Preset speed 8
1 = 1
U16
P5‐07
507
Fieldbus ramp control
0: Disable
1: Enable
1 = 1
U16
P5‐08
508
Anybus module output process data 4
1: Power (x.xx kW)
2: Digital input status
3: 2
nd
analog input (%)
4. Power stage temperature
1=1
U16