APPLICATION NOTE AN‐BEI‐H2‐038
Date: 15/02/12
AN‐BEI‐H2‐038 Modbus RTU Control and Register Mapping
11
Group 8 : Application Specific Parameters ‐ Level 3
Parameter
Register
Number
Description
Range
Scaling
Type
P8‐01
801
Stir Function Interval Time
0 to 6000
U16
P8‐02
802
Stir Activity Time
1 to 6000
U16
P8‐03
803
Pump Clean Function Configuration
0 : Disabled
1 : Active on Start Only
2 : Active on Torque Detection Only
3 : Active on Start & Over Torque Detection
U16
P8‐04
804
Clean Time interval
0 to 600
U16
P8‐05
805
Pump Clean Function Ramp Time
0 to 60000
1 = 0.1s
U16
P8‐06
806
Load Profile Monitor Function Enable
0 : Disabled
1 : Low Load Detection
2 : High Load Detection
3 : Low & High Load Detection
U16
P8‐07
807
Load Profile Monitoring Bandwidth
10 to 1000
10 = 1.0A
U16
P8‐08
808
Load Profile Monitoring Trip Delay
0 to 60
U16
P8‐09
809
Fire Mode Logic
0 : Open Activation (Normally Closed)
1 : Closed Activation (Normally Open)
U16
P8‐10
810
Fire Mode Speed
‐7200 to 7200 (Limited by P1‐01)
3000 = 50.0Hz
S16
P8‐11
811
Bypass Mode On Fault
0 : Disabled
1 : Enabled
U16
P8‐12
812
Bypass Mode On Fire
0 : Disabled
1 : Enabled
U16
P8‐13
813
Bypass Contactor Changeover Time
0 to 300
1 = 0.1 s
U16
P8‐14
814
Pump Staging Function Select
0 : Disabled
1 : Single Drive, Fixed Speed Assist
2 : Multi Drive Optiflow Control
U16
P8‐15
815
Pump Staging Additional Pumps
0 to 4
U16
P8‐16
816
Pump Staging Duty Switchover Time
0 to 1000
U16
P8‐17
817
Pump Staging DOL Switch in speed
0 to 7200 (Limited by P1‐01)
3000 = 50.0Hz
U16
P8‐18
818
Pump Staging DOL Switch out speed
0 to 7200 (Limited by P1‐01)
3000 = 50.0Hz
U16
P8‐19
819
Pump Staging System Settle Time
10 to 600
U16
P8‐20
820
Pump Staging Master Clock Reset
0 : No Function
1 : Reset Timer
U16