APPLICATION NOTE AN‐BEI‐H2‐038
Date: 15/02/12
AN‐BEI‐H2‐038 Modbus RTU Control and Register Mapping
5
Register 8: Output Current
This register displays the output current from the drive.
The data is 16bit integer with one decimal place. E.g. 156 = 15.6A, 12 = 1.2A.
Register 10: Output Power
This register displays the output power level.
The data is 16bit integer with two decimal places. E.g. 1000 = 10.00kW
Register 11: Digital input status
The value in this register represents the digital status of the drive control input terminals. Bit 0 indicates the status of Input 1, Bit
1 indicates the status of Input 2 etc...
Register 12: Rating ID
The value in this parameter includes specific drive ID information, and is not recommended to be used by customer. For more
information regarding this parameter, please contact your local drive sales partner.
Register 13: Power rating
This gives the drive power rating information to two decimal places, e.g. 075 = 0.75. The unit of this register depends on the
drive type (KW/HP)
Register 14: Supply Voltage level
This register gives the rated input voltage for the drive.
i.e.
230 : 230V nominal (200 – 240 + / ‐ 10%)
400: 400V nominal (380 – 480 + / ‐ 10%)
460: 460V nominal (380 – 480 Volts + / ‐ 10%)
Register 15: IO software version
This register contains the drive IO software version info. The value includes two decimal places.
i.e. 100 means version 1.00
Register 16: Motor control processor software version
This register contains the software version info of the motor control processor. The value includes two decimal places. E.g. 100
means version 1.00
Register 17: Drive type
This register gives the drive internal type code.
Register 20: Analog input 1 value
This register gives the value of the analog signal applied to analog input 1 after any scaling and offsets have been applied. The
value is a 16 bit integer where a returned value of 4096 represents the maximum input value, e.g. 100%.
Register 21: Analog input 2 value
This register gives the value of the analog signal applied to analog input 2 after any scaling and offsets have been applied. The
value is a 16 bit integer where a returned value of 4096 represents the maximum input value, e.g. 100%.
Register 22: Pre Ramp Speed Reference Value
This register contains the reference speed information that being used by the drive for motor speed control. The data is in Hz
and with one decimal place (i.e. 234 = 23.4Hz)
Register 23: DC bus voltage
This register contains drive internal DC bus voltage information. The value is displayed as volts, with no decimal places.
Register 24: Drive temperature
This register contains drive temperature information. Data is in Celsius with no decimal place.