Fault Tracing
11
Fault Tracing
This section includes different fault scenarios and steps to follow to trace the fault.
The iX Panel TA100 is not working properly, and the
power LED is off
1. Is the power voltage correct?
2. Does the power supply deliver enough current?
3. Check the fuse.
4. Check the power card.
5. Is the power card correctly mounted?
The iX Panel TA100 is not communicating with the
controller
1. Check the communication cable between the units.
2. Check that the operator panel has a controller driver downloaded.
3. Check that the correct controller driver is used.
4. Check the communication ports on the CPU board.
The iX Panel TA100 is working but the backlight is off
1. Check the backlight dimming.
2. Check that the backlight is connected to the power card.
3. Replace the backlight according to the
section.
4. Check the DC/AC on the power card.
The iX Panel TA100 is not working, the backlight is off
but the power LED is on
1. Check the backlight dimming.
2. Check the CPU board for burned components.
3. Download new firmware to the operator panel.
The iX Panel TA100 does not include the latest image
1. Check the versions included with the operator panel.
2. Make sure to save a copy of the project to the PC.
3. Download an updated image with the Image Loader and follow the directions
in the
section.