Without Ratio Control – Coarse Adjustment

1. Place the override switch in the “out” or manual position. The pump need not be running for

coarse adjustment.

2. Set up a voltmeter to read a full scale DC voltage of 10.

3. Connect the positive lead of the voltmeter to TB2-2 and the negative lead to TB2-1.

4. Set the control signal at the low end (0%) and record the voltage.

5. Set the control signal at the high end (100%) and record the voltage.

6. Set up a voltmeter for DC voltage measurement between TB2-5 (positive) and TB2-1

(common).

7. Adjust the “LO” trim potentiometer on the circuit board to the voltage recorded in step 4.

8. Set up the voltmeter for DC voltage measurement between TB2-4 (positive) and TB201

(common).

9. Adjust the “HI” trim potentiometer on the circuit board to the voltage recorded in step 5.

10. The above adjustments are interactive. It may be necessary to repeat steps (2) through (5)

several times until the voltages stabilize. This completes coarse adjustment.

Without Ratio Control – Fine Adjustment

11. With the override switch still in the “out” or manual position start the pump.

12. Set up a voltmeter for DC voltage measurement between TB2-3 (positive) and TB2-1

(common).

13. Set the control signal at the low end (0%). Move the override switch to the “in” or auto

position. The LO” drive LED will light and the pump with automatically adjust to the 0%
stroke.

14. Adjust the “LO” trim potentiometer on the circuit board to the voltage recorded in step (4).

The stroke indicator should now read 000-001 and both LED drive lights should be off.

15. Apply a high end (100%) control signal. Allow the pump to adjust to 100% stroke.

16. With the voltmeter remaining as set up in step (12) above, adjust the “HI” trim potentiometer

to the voltage recorded in step (5). The stroke indicator should now read 099-100 and again
both drive lights should be off.

17. The above adjustments are interactive. It may be necessary to repeat steps (12) through (16)

several times until the voltages stabilize. This completes fine adjustment.

With Ratio Control (Optional Feature) – Coarse Adjustment

1. With the override switch in the “out” or manual position, start the pump.

2. Set the controls signal at the low end (0%). Move the override switch “in” to the auto position

and allow the pump to adjust to 0%.

3. Place the override switch back in the “out” or manual position. Check the stroke indicator; if it

does not read 000-001 use the handwheel to manually adjust it to this point.

4. Set the remote ratio control potentiometer at 100%.

5. Set up the voltmeter for DC voltage measurement between TB3-4 (positive) and TB3-6

(common).