beautypg.com

Operation – Nor-Lake AdvantEDGE Bottom Mount Refrigerators & Freezers User Manual

Page 2

background image

08/13 Rev. C 146527

2


Confirm that the proposed electrical outlet has the correct voltage, frequency and
current carrying capacity for the requirements of the unit. This information is noted on
the data plate on the inside left wall of the unit. The unit should be isolated on a circuit.
Do not use an extension cord to get power to the unit. Improper electrical installations
will void the compressor warranty.

OPERATION

Once the unit is connected to the proper power supply, the display panel will be lit for
two (2) seconds followed by a beep, the cabinet temperature will be displayed and the
compressor will start to run. The compressor is running whenever ‘COMP’ is lit on the
display. If the cabinet temperature is higher than +68

˚F (refrigerator) or +14˚F

(freezers), the display will read . If the cabinet temperature is lower than +14

˚F

(refrigerator) or -50

˚F (freezer), the display will read . If the unit does not start

immediately, check the power switch located on the bottom of the top grill. If the cabinet
temperature is below +14

˚F (freezer) or +50˚F (refrigerator) when the unit is plugged in,

there will be a three minute delay before the compressor will start.

The interior light will come on when a door is opened.

Whenever a door is opened, the door open light on the display will be lit and the
evaporator fans will stop. The fans will start three seconds after the door is closed. If a
door is open for more than 30 seconds, the door open alarm will beep two times. If a
door is open more than 60 seconds, the alarm beeps five times and if open more than
five minutes, the alarm will beep continuously.

The electronic control has an alarm function to remind the operator to periodically clean
the condenser coil. The condenser coil will collect dust and debris during normal
operation. If left unclean, this will lead to poor performance, high energy consumption
and possible compressor failure. Warranties do not cover failures related to condenser
cleaning. At 6 month intervals, the display will blink “CL” and the buzzer will sound to
remind the operator to clean the condenser coil. After one hour, the buzzer will stop but
the display will continue to blink “CL”. Refer to the ‘MAINTENANCE’ section of this
manual to learn how to clean the condenser coil. The electronic control can be reset to
normal operation by pressing the ‘Mode’ and ‘Verify’ buttons at the same time for five
seconds. Depending on conditions, the condenser coil may require more frequent
cleaning.

When a door is closed on a cabinet that is running, an internal vacuum is created as the
internal air is cooled and the door can be difficult to open for awhile. These units
incorporate a pressure relief valve that equalizes the vacuum to allow the door to be
opened sooner.