Symmetra PX 160 kW 400 V Operation

990-3015-001

PDU fault list

Display Message

Meaning

Corrective Action

Maintenance Bypass Alarm The system is in maintenance

bypass: the Q2 switch is open
and the Q3 switch is closed.

No corrective action necessary.

Output V

Voltage Under Limit

Phase-to-neutral output voltage
for phase has dropped
below the configured limit.

Evaluate the threshold setting. If necessary,
adjust it for your situation.

Output V
Voltage Over Limit

Phase-to-neutral output voltage
for phase exceeded the
configured limit.

Evaluate the threshold setting. If necessary,
adjust it for your situation.

Output I L
Current Over Limit

Current of output phase
exceeded the configured limit.

Evaluate the threshold setting. If necessary,
adjust it for your situation.

Output I L
Current Under Limit

Current of output phase
dropped below the configured
limit.

Evaluate the threshold setting. If necessary,
adjust it for your situation.

Output FDev
Freq Out of Range

Frequency of the output current
is above or below the range that
is configured as acceptable.

Evaluate the threshold setting. If necessary,
adjust it for your situation.


Alarm Active

A user-configured contact
connected to the system is
reporting an alarm condition.

Determined why the alarm has occurred. This
is a user-specific alarm setting.

No UPS Input
Breaker Q1 Open

The Q1 circuit breaker is open,
and the UPS is disconnected
from the input voltage.

Close the Q1 switch to re-connect the UPS to
utility/mains power.

No Panel Feed
Breakers Q2 & Q3 Open

The Q2 & Q3 circuit breakers
are open, and the system is not
supporting connected
equipment.

For safety reasons, ensure the switches were
not closed for maintenance purposes. If not,
close Q2 for UPS operation, and Q3 for
maintenance bypass.

Atypical Bypass Mode
Alarm

The system state as set by the
Q1, Q2, & Q3 breakers is in a
non-typical bypass mode.

Option 1: Resume normal UPS operation.
Option 2: Go to maintenance bypass.