beautypg.com

How to view the status screens, Press, How to view the log screen – APC SYMMETRA PDUM160H-B User Manual

Page 18

background image

Operation: Operation Procedures

12

Symmetra PX 160 kW 400 V Operation

990-3015-001

Press

E

SC

to go back to the UPS Control screen and select UPS into Bypass

.

Note: The H2 LED next to the Q2 switch will illuminate, indicating that it is safe to

operate the Q2 switch.

Set the Q2 switch on the PDU-XR or external maintenance bypass panel to the ON position.

Note: The H3 LED next to the Q3 switch will illuminate, indicating that it is safe to

operate the Q3 switch.

Set the Q3 switch on the PDU-XR or external maintenance bypass panel on the PDU-XR to the

OFF position. As soon as the Q3 switch is in the OFF position, the UPS will automatically return

from maintenance bypass operation to normal operation.

The UPS is now in normal operation. Verify that the Load Powered LED is lit and the system is not
displaying any alarms.

How to view the Status screens

Use the main menu screen to access information for each component of the system. A status screen is
available for each component, this example uses the UPS.

How to view the Log screen

Press

Press

Press Use

the

UP

and

DOWN

arrow keys to navigate

through the Status screens.

UPS

Alarms

Power Dist
Switch Gear
Environment

Log
Admin
Help

UPS Control
UPS Status
UPS Tests & Diags
UPS Configuration

Symmetra PX 160 kW
On Line

No UPS Alarms


Press

Press

Use the

UP

and

DOWN

arrow keys to navigate

through the Log screens.

UPS

Alarms

Power Dist
Switch Gear
Environment

Log
Admin
Help

View New Log Items

View Entire Log
Clear Entire Log

Log Item > 1 of 2

<Description>

03/14/07 10:37:02

This manual is related to the following products: