Operation procedures, Total power off procedure – APC SYMMETRA PDUM160H-B User Manual

Page 14

background image

8

Symmetra PX 160 kW 400 V Operation

990-3015-001

Operation Procedures

Note: If the system does not contain a PDU-XR, the Q1, Q2, Q3, and Q5 switches are located
on an optional external maintenance bypass panel. Refer to the documentation included with the
maintenance bypass panel for additional information.

Total Power Off procedure

Warning: Before electrical installation begins, verify that the UPS is in the Total Power Off
mode by following this procedure.

Set the

S

YSTEM

E

NABLE

switch to the the OFF

position.

Set the

DC D

ISCONNECT

switch on all XR Battery enclosures and on the back of the PDU-XR to the

OFF position.

Disconnect all battery units by removing them or pulling them out to the red disconnect line.

Caution: To ensure the enclosure does not tip, do not pull the battery units out beyond

the red disconnect line unless you completely remove them from the enclosure.

ON

TRIP

OFF

UPS

XR Battery enclosures / PDU-XR