Operation: Operation Procedures

990-3015-001

Symmetra PX 160 kW 400 V Operation

11

How to return to normal operation

Set the

DC D

ISCONNECT

switch on all of the XR Battery enclosures and the PDU-XR to the ON

position.

Set the Q1 switch on the PDU-XR or external maintenance bypass panel to the ON position.

Set the Q5 switch

on the PDU-XR or external maintenance bypass panel to the ON position.

Set the

S

YSTEM

E

NABLE

switch on the UPS to the ON position.

Note: Wait approximately 30 seconds for system to start.

Using the display interface, select the following:

Press

Press

Press

Press

UPS

Alarms

Power Dist
Switch Gear
Environment

Log
Admin
Help

UPS Control
UPS Status
UPS Tests & Diags
UPS Configuration

Turn UPS On
UPS On Into Bypass

UPS Load is ON.