2.4.3 CWS655 Environmental Specifications

Temperature Range: -25° to +50°C (-13° F to + 122°F)

Humidity Range:

0 to 100%

Weather Resistance: IP67 rating for sensor and battery pack (battery pack

must be properly installed; each sensor is leak tested)

2.5 CWS900 Specifications

2.5.1 CWS900 Physical Specifications

Dimensions:

15 cm x 6 cm x 4.5 cm (6” x 2.4” x 1.8”)

Weight:

184 g (6.5 oz)

2.5.2 CWS900 Electrical Specifications

Power: 2

AA

Batteries

Average Current Drain:

300

μA with 15 minute polling (depending

on attached sensor)

Radio:

Internal 25 mW FHSS Radio

Single-Ended Analog Channels:

SE1, SE2, SE3

Differential Analog Channels:

DF1

Analog Input Range:

-1 to + 2.5 VDC

Accuracy:

±(0.02% of reading + 2 µV) @ 0° to +50°C;
±(0.05% of reading + 2 µV) @ -35° to +70°C

Resolution:

0.3

μV

Excitation Voltage:

2.5V, 3.3 V, 5.0 V
20 mA maximum

Excitation Voltage Accuracy:

±2% @ -35° to +70°C

Bridge Measurement Accuracy
(+2.5 excitation only):


±(0.03% of reading + 3 µV) @ 0° to + 50°C;
±(0.07% of reading + 3 µV) @ -35° to + 70°C

Low Level AC Input:

20 mV minimum
10 kHz maximum frequency

Switch Closure

Maximum Count Rate:

Minimum Open Time:

Minimum Closed Time:

Maximum Bounce Time:


100 Hz
5 ms
5 ms
4 ms

Temperature Accuracy:

± 0.2ºC