beautypg.com

Installation – Campbell Scientific CS11-L Current Transformer User Manual

Page 8

background image

CS11-L Current Transformer

Measurement Ranges:

0.15 to 200 A (0.15 to 125 A for CR200X)

Frequency:

50 and 60 Hz

Insulation Resistance:

100 M ohm @ 500 Vdc

High Potential: 2000

volts

Rated Current:

200 A, 125 A (CR200X)

Storage Temperature: –25º

to

70ºC

Operating Temperature: –25º

to

55ºC

Case Material: Polypropylene

Resin

Construction: Epoxy

Encapsulated

Accuracy with 10 ohm
Burden Max. (resistive):
Typically

±1 percent of actual value with

provided multiplier

Dimensions

Outer Diameter:

4.8 cm (1.89 in)

Inner Diameter:

1.9 cm (0.75 in)

Height:

1.7 cm (0.67 in)

Multiplier:

i

Mult

=200 A/1000mV=0.2

3. Installation

Place one AC wire through the hole of the CS11-L (see FIGURE 3-1). The
sensor may be placed on either the hot or neutral AC wire.

FIGURE 3-1. AC load wire installed in CS11-L (color of ac load wire

can vary)

2