CS11-L Current Transformer
10: Do (P86)
1: 3
Call
Subroutine
3
11: Z=X (P31)
1: 3
X Loc [ Burst_A2 ]
2: 5
-- Z Loc [ CS11_2 ]
12: End (P95)
13: Do (P86)
1: 51
Set
Port
1
Low
; This part of the program will store a one minute average of the amperage.
14: If time is (P92)
1: 0
Minutes (Seconds --) into a
2: 1
Interval (same units as above)
3: 10
Set Output Flag High (Flag 0)
15: Set Active Storage Area (P80)^17815
1: 1
Final
Storage
Area
1
2: 60
Array
ID
16: Real Time (P77)^10331
1: 1220
Year,Day,Hour/Minute
(midnight
=
2400)
17: Average (P71)^5143
1: 64
Reps
2: 4
Loc [ CS11_1 ]
*Table 2 Program
02: 0.0000 Execution
Interval
(seconds)
*Table 3 Subroutines
;
; Parameter 2 should be 2500 mV for 50-200 amps
; should be 250 mV for 5-49 amps
; should be 25 mV for 0-4.9 amps
; Parameter 5 should be 2.0 msec for 50 Hz or 60 Hz
; Parameter 6 should be 0.05 thousand scans for 50 Hz or 60 Hz
; if parameter 5 & 6 are 2.0 and 0.05, then you have 5 complete cycles at 50 Hz
; or 6 complete cycles at 60 Hz.
1: Beginning of Subroutine (P85)
1: 1
Subroutine
1
2: Burst Measurement (P23)
1: 1
Input Channels per Scan
2: 15
2500
mV
Fast
Range
3: 1
In
Chan
4: 0001
Trig/Trig/Dest/Meas
Options
5: 2.0
Time
per
Scan
(msec)
6: .05
Scans
(in
thousands)
7: 0
Samples
before
Trigger
8: 0.0
mV
Limit
9: 0000
mV
Excitation
20