4 03101 anemometer, 5 03301 vane, Wiring – Campbell Scientific 03001-L R.M. Young Wind Sentry Set User Manual
Page 10
R.M. Young Wind Sentry
3.4 03101 Anemometer
Install the cupwheel to the anemometer shaft using the Allen wrench provided
with the sensor.
The 03101 mounts to a threaded 0.75” IPS schedule 40 pipe (1.05” O.D.). A
10” long mounting pipe ships with the 03101 for attaching the sensor to a
019ALU or CM200 series crossarm with CM220 (Figures 3-3) or PN 1049.
The 03001 can also be mounted at the top of a CM6/CM10 tripod mast, or to a
CM110 series tripod with the CM216.
Mount the 019ALU or CM200 series crossarm to the tripod or tower. Screw
the mounting pipe into the base of the 03101, and attach the sensor / mounting
pipe to the crossarm.
Route the sensor cable along the underside of the crossarm to the tower/tripod
mast, and to the instrument enclosure. Secure the sensor cable to the crossarm
and mast using cable ties.
3.5 03301 Vane
The 03301 Vane is typically ordered as a replacement vane for the 03001
Wind Sentry Set, and includes the bracket for attaching it to the 03001
crossarm. PN 4913 pipe mount (not included with the sensor) can be used to
attach the 03301 to a 019ALU or CM200 series crossarm (with the CM220 or
PN 1049), and the mounting pipe that ships with the sensor.
4. Wiring
Connections to Campbell Scientific dataloggers are given in Table 4-1. When
Short Cut for Windows software is used to create the datalogger program, the
sensor should be wired to the channels shown on the wiring diagram created
by Short Cut.
TABLE 4-1. Connections to Campbell Scientific Dataloggers
Color
Description
CR800
CR5000
CR3000
CR1000
CR510
CR500
CR10(X)
CR21X
CR7
CR23X
CR200
Black
Wind Spd. Signal
Pulse
Pulse
Pulse
P_LL
White
Wind Spd. Reference
G
Clear
Wind Spd. Shield
G
Red
Wind Dir. Signal
SE Analog
SE Analog
SE Analog
SE Analog
Black
Wind Dir. Excitation
Excitation
Excitation
Excitation
Excitation
White
Wind Dir. Reference
AG
Clear
Wind Dir. Shield
G
6