Samlex America MSK-135 User Manual
Page 12
![background image](/manuals/415636/12/background.png)
12 | SAMLEX AMERICA INC.
reD - steady
“oVer DISCHArGe”: protection against over discharge of
battery has been activated at ≤ 11.1V / ≤ 22.2V and the load
has been disconnected.
Load will be reconnected automatically at 12.6V / 25.2V and
the LeD will go back to steady green from steady red
5D. Status LeD “Flooded”: flooded Type of battery has been selected
5e. Status LeD “Gel”: Sealed, Gel Cell Type of battery has been selected.
5f. Status LeD “Sealed”: Sealed, AGM type of battery has been selected.
5G. Status LeD “Load” Load Status indicator: display the Load Status.
LeD coLoR
AnD PAtteRn
StAtUS
StAtUS
reD - flashing
reD - Steady
over Load or Short circuit”: Load has been disconnected
due to overload or short circuit in the load circuit con-
nected to the Load Terminals
overload: 12.5A for 5 sec – Manual reset by pressing
“Set” button
Short circuit: 35A – first short circuit is reset
automatically after 10 sec. Second consecutive short circuit
will require manual reset by pressing “Set” button
Load is oN
5H. Setting button:
- Switch oN and Switch off the load connected to the Load Terminals.
- Select battery type
5I. Terminals for connecting Solar Module
5J. Terminals for connecting battery
5K. Terminals for connecting Load(s) - Maximum 10A
!
cAUtion!
Please note that the Solar Modules are permanently connected to the input terminals
of the charge controller. the modules will start generating power as soon as these are
exposed to sunlight. However, there will be no power output from the charge control-
ler until the controller is connected to the battery. Make sure that the battery voltage is
> 6v in order to start the charge controller. the following spurious LeD indications may
be seen at the charge controller and may be disregarded:
SectIOn 3 |
Installation & Operation