Samlex America SA-1500 User Manual
Page 32
30
9-2-6. Power saving “sleep” mode, disabled
9-2-6-1. The front plate has a green led marked “power saving” for
indication of enable state of power save “sleep” mode (here-
in-after referred to as the green led).
9-2-6-2. The power saving “sleep” mode is disabled when the green
led marked “power saving” is off. In this mode the output
power is always available.
9-2-6-3. Following indications will be observed when the inverter is
powered on and subsequently loaded and unloaded when
power saving “sleep” mode is in disabled condition: (the initial
condition is that the inverter is switched off and all loads are
disconnected).
9-2-6-3-1. Switch on the inverter. There will be 2 beeps and
green led will start flashing with a flashing
sequence of flash-flash-flash… After about 3
seconds, there will be 1 beep and the green led
will stop flashing and switch off. Output power will
be available after about 15 to 18 sec from the time
the green led switches off. The output power will
be always available, even in no load idling
condition.
The green led will be off all the time.
9-2-7. Switching between enabled and disabled states of power saving
“sleep” mode
9-2-7-1. Switching between enabled and disabled states of power
saving “sleep” mode can be done with the help of the power
on / off switch on the front plate of the inverter or with the help
of the optional remote control.
Switch on the front plate of the inverter is done as follows: