3-5. Making DC Wiring Connections

Follow this procedure to connect the battery cables to the DC input terminals

of the Inverter. Your cables should be as short as possible (ideally, less than

6 feet / 1.8 meters) enough to handle the required current in accordance with

the electrical codes or regulations application. Cables are not an adequate

gauge (too narrow) or too long will decrease the inverter performances such

as poor surge capability and low input voltage warnings frequently and

shutdowns. UVP warning presents due to DC voltage drop across the cables

from the inverter to the batteries.

The longer or narrower the cables, the greater the voltage drop.

Increasing your DC cable size will help improve the situation.

Model No

Wire AWG

Inline Fuse

SA-1500-112

# 2

200A

SA-1500-124

# 4

130A

WARNING!
The installation of a fuse must be on positive cable.
Failure to place a fuse on “+” cables running between

the inverter and battery may cause damage to the

inverter and will void warranty.