beautypg.com

Type of gas, Vii initial start-up – Midco G69B User Manual

Page 7

background image

20

350
550

730

1150
1100
1730

2100
2500
2500

-7-

CAUTION: Do not exceed maximum rated capacity

of burner model - See Tables 1 and 2.
Capacities shown are for total pressure drop of .3"W.C. For
higher permissible pressure drops consult your fuel
supplier.

Source: Gas Engineers HandbookÑ1974

TABLE 3

Schedule 40 Pipe Capacity Chart

Before gas is introduced to the system, a check must be
made to see that there are no open fittings and to make
sure the burner main and pilot manual valves are closed.
After checking above, purge the gas line up to the burner
inlet. Purging the air from the gas supply line at this step
will expedite the first light-off.

CAUTION: Purge outside the building. Do not

purge into the gas utilization equipment combustion
chamber.

Gas Supply

Pipe Size

N.P.T.

1"

1-1Ъ4"

1-1Ъ2"

2"

2 -1Ъ2"

3"

Type of

Gas

Natural

Propane

Natural

Propane

Natural

Propane

Natural

Propane

Natural

Propane

Natural

Propane

APPROXIMATE CAPACITY-MBH

Length of Pipe Ñ Feet

40

385
500
785
760

1200

1450
2280
2300
2500
2500

60

300
400
630
610
960

1150
1800
1850
2500

2500

100

300
480
460
725

870

1370
1400
2200

2500
2500

200

330
320
500

610
960
980

1550

1700
2500

MAIN REGULATOR

MAIN REGULATOR

VENT

PILOT MANUAL

VALVE

BALL

VALVE

PILOT

REGULATOR

BLOWER

MOTOR

MANUAL MOTOR RESET

BUTTON

(MAY HAVE AUTO RESET)

MANIFOLD PRESSURE

TAP

DRIP LEG

REDUNDANT MAIN

AUTOMATIC VALVES

BF INPUT ADJUSTER

(HIDDEN)

BALL VALVE

PILOT SOLENOID

VALVE

PILOT MIXING

TEE

PILOT

PRESSURE TAP

PEEP SIGHT

PILOT AIR

TUBE

RESET

BUTTON

BLOWER

AIR

SWITCH

FLAME SAFEGUARD

CONTROL

INLET PRESSURE TAP

1/4 TEE

1/4 PLUG

FIGURE 11

Piping Connections

VII

INITIAL START-UP

WARNING: Repeated unsuccessful attempts to

light may result in accumulated gases in gas
utilization equipment and chimney. To prevent these
gases from reaching an explosive level, periodically
purge the gas utilization equipment.

CAUTION: All cover plates, guards, and

enclosures must be maintained in place at all times
except during maintenance and servicing.

CAUTION:

Optional equipment and/or special

limit controls such as high/low gas pressure switches
can alter the start-up procedure. See Section XIV-
SPECIAL EQUIPMENT.
1.

Check the piping for leaks. A quick way to do this is to

close the main manual shut-off valve and manual
pilot valve, then turn on the gas pressure to the gas
supply line and observe the meter test dial. There
should be no movement of the test dial hand for at
least twenty minutes. All other gas appliances must be
completely shut off during this test (including pilots). If
a leak is detected it should be located with a soap
suds test. Test the main automatic valve for tightness.
(see Section XII for instructions). The ball valve is
intended to be open at all times except when testing
for main valve leakage. The Main Manual Shut-Off
Valve must be used for manual gas shut-off.

2.

Make sure that the burner main and pilot gas lines are

completely purged of air. Do not purge into the
combustion chamber. Purge outside the building.

3.

Make sure the burner power switch is off, manual

valve is closed, pilot manual valve is closed,
motor is free to rotate, and flame safeguard reset
button is set.

4.

Make the proper settings on all limit controls and set

controller to call for heat.

5.

Set blower air shutter wide open.

This manual is related to the following products: