Type mode feature, Electrical specifications, Ordering information – Notifier UDACT User Manual
Page 2

Page 2 of 4 — dn-4867:b • 03/27/09
NOTE: Ademco Contact ID must be used for independent zone
reporting.
Type Mode Feature
Ademco Contact ID format only) Use Type Mode to identify
reports to Central Station as:
• Fire Alarm
• Burglary
• Supervisory
• 24 hour Non-Burglary
• Pull Station
• High Temperature
• Heat Detector
• Low Temperature
• Waterflow
• Low Water Pressure
• Duct Detector
• Low Water Level
• Flame Sensor
• Pump Failure
• Smoke Zone
Electrical Specifications
Standby current: 40 mA.
Current while communicating: 75 mA.
Maximum current while communicating and with open collec-
tor output activated
: 100 mA.
Voltage: Regulated 24 volts. Range: 21.2 to 28.2 volts.
Ordering Information
UDACT: Universal Digital Alarm Communicator Transmitter.
Includes operating and programming instructions, and mount-
ing hardware.
MCBL-7: DACT phone cord, 7 ft (2.13 m) long (two required).
ABS-8RB: Metal enclosure for externally mounting UDACT
up to 6,000 ft./1828.8 m from host FACP. 9.94" H x 4.63" W x
2.50" D (cm: 25.248 H x 11.760 W x 6.350 D).
UBS-1: Metal enclosure. Includes viewing window and
optional relay mounting capability.
R-10E: SPDT Form-C relay. Contacts rated for 10 A @ 115
VAC. Connects to open collector relay driver.
R-20E: DPDT Two Form-C relays. Contacts rated for 10A @
115 VAC. Connects to open collector relay driver.
FBD-1: Ferrite bead kit. Use for remote mounting only.
ROM1-UDACT: EPROM upgrade kit.