Tone selection, Chime patterns – Notifier Chime Strobes User Manual
Page 3

dn-7089:a3 • 4/20/10 — Page 3 of 4
Tone Selection
Chime tone selection is accomplished by using the rotary switch on the back
of the product. The current draw and sound measurements for various
chime tones are listed below.
Chime Current Draw,
UL Maximum (mA RMS)
Sound Output (dBA), Chime and Chime/Strobe
SpectrAlert Advance Chime/Strobe Dimensions
Sound Pattern
dB
8 – 17.5 Volts
16 – 33 Volts
DC
FWR
DC
FWR
1-Second Chime
HIGH
34 mA
50 mA
58 mA
51 mA
1-Second Chime
LOW
30 mA
51 mA
51 mA
54 mA
1/4-Second Chime
HIGH
34 mA
51 mA
50 mA
50 mA
1/4-Second Chime
LOW
31 mA
51 mA
50 mA
52 mA
Temporal Chime
HIGH
30 mA
50 mA
48 mA
54 mA
Temporal Chime
LOW
30 mA
47 mA
50 mA
51 mA
5-Second Whoop
HIGH
32 mA
52 mA
34 mA
54 mA
5-Second Whoop
LOW
30 mA
40 mA
34 mA
52 mA
One Test Chime
HIGH
48 mA
49 mA
50 mA
50 mA
Switch
Setting
Sound Pattern
dB
8 – 17.5 Volts
16 – 33 Volts
DC
FWR
DC
FWR
1
1-Second Chime
HIGH
58 dBA 59 dBA 61 dBA 61 dBA
2
1-Second Chime
LOW
53 dBA 54 dBA 55 dBA 55 dBA
3
1/4-Second Chime
HIGH
63 dBA 64 dBA 66 dBA 66 dBA
4
1/4-Second Chime
LOW
58 dBA 59 dBA 60 dBA 60 dBA
5
Temporal Chime
HIGH
62 dBA 64 dBA 68 dBA 69 dBA
6
Temporal Chime
LOW
55 dBA 57 dBA 60 dBA 60 dBA
7
5-Second Whoop
HIGH
68 dBA 71 dBA 75 dBA 77 dBA
8
5-Second Whoop
LOW
62 dBA 64 dBA 67 dBA 68 dBA
9
One Test Chime
HIGH
57 dBA 55 dBA 61 dBA 57 dBA
Chime Patterns
Setting
Repetition Rate
dB Out
1
1-Second Chime
HIGH
2
1-Second Chime
LOW
3
1/4-Second Chime
HIGH
4
1/4-Second Chime
LOW
5
Temporal Chime
HIGH
6
Temporal Chime
LOW
7
5-Second Whoop
HIGH
8
5-Second Whoop
LOW
9
One Test Chime
HIGH
7089dim1.tif