Notifier Field-Selectable Mass Notification Devices User Manual
Page 3

DN-60517:A • 06/02/2009 — Page 3 of 6
UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Standard Candela Range (15–115 cd)
8–17.5 Volts
16–33 Volts
15 15/75 15 15/75 30 75 95 110 115
DC Input
Temporal
High
137 147 79 90 107 176 194 212 218
Temporal
Medium
132 144 69 80 97 157 182 201 210
Temporal
Low
132 143 66 77 93 154 179 198 207
Non-Temporal
High
141 152 91 100 116 176 201 221 229
Non-Temporal
Medium
133 145 75 85 102 163 187 207 216
Non-Temporal
Low
131 144 68 79 96 156 182 201 210
FWR Input
Temporal
High
136 155 88 97 112 168 190 210 218
Temporal
Medium
129 152 78 88 103 160 184 202 206
Temporal
Low
129 151 76 86 101 160 184 194 201
Non-Temporal
High
142 161 103 112 126 181 203 221 229
Non-Temporal
Medium
134 155 85 95 110 166 189 208 216
Non-Temporal
Low
132 154 80 90 105 161 184 202 211
UL Max. Current Draw (mA RMS), 2-Wire Horn
Strobe, High Candela Range (135–185 cd)
16–33 Volts
135 150 177 185
DC Input
Temporal
High
245 259 290 297
Temporal
Medium 235 253 288 297
Temporal
Low
232 251 282 292
Non-Temporal
High 255 270 303 309
Non-Temporal
Medium
242 259 293 299
Non-Temporal
Low 238 254 291 295
FWR Input
Temporal
High
215 231 258 265
Temporal
Medium 209 224 250 258
Temporal
Low
207 221 248 256
Non-Temporal
High 233 248 275 281
Non-Temporal
Medium
219 232 262 267
Non-Temporal
Low 214 229 256 262