beautypg.com

Signal, Mt signal – Notifier Series MT User Manual

Page 3

background image

DN-4855 • 03/30/04 — Page 3 of 4

+

-

+

-

TO NEXT

APPLIANCE OR

EOLR

+

-

FROM
PRECEDING
APPLIANCE,
SM/DSM,
PS-12/24-8MP
POWER SUPPLY
or FACP

SIGNAL

ORDERING INFORMATION

WIRING DIAGRAMS (for all models)

TO NEXT
AUDIBLE OR
EOLR

FROM
PRECEDING
AUDIBLE OR
FACP

TO NEXT
STROBE OR
EOLR

FROM PRECEDING
APPLIANCE,
SM/DSM,
PS-12/24-8MP
POWER SUPPLY
OR FACP

AUDIBLE

STROBE

+

-

-

+

+

-

-

-

-

+

+

+

MT Signal

TO NEXT

APPLIANCE

OR EOLR

FROM
PRECEDING
APPLIANCE
OR FACP

+ -

STROBE

AUDIBLE

+ -

RED

BLACK

+

-

-

+

Audible signal and strobe operate

independently

Audible signal and strobe operate in unison.

Red and black shunt-wires are supplied.

NOTE

: Do NOT loop wires under terminals; use In/

Out wiring method per NFPA/NEC.

+

MT-12/24 Audible can be used with Wheelock’s RSSP Multi-Candela for applications requiring 15, 30, 75, 110

cd Wall Strobes.
**MTWP-2475W is Weatherproof and rated for 75 cd @ -31°F (-35°C). See Wheelock Data Sheet S9004 or
Installation Instruction P84150.
***For additional information on mounting please refer to Data Sheet S7000.
****SM Sync Modules are rated for 3.0 amperes at 12/24 VDC; DSM Dual Circuit Modules are rated for 3.0
amperes per circuit. Maximum number of interconnected DSM modules is twenty (20). Refer to Wheelock
Data Sheet S3000.
# Use MT-241575W when 15cd is specified. 15/75 is UL Listed for 15cd with 75cd on AXIS.

## Series WH Strobe is listed for UL Standard 1638 only. See Wheelock Instruction Sheet P83159.

NOTE:

Due to continous development of products offered by NOTIFIER, specifications and product availability are subject

to change without notice in accordance with NOTIFIER standard terms and conditions.

UL

MEA CSFM FM

BFP

MT-12/24-R*

12/24

-

D,E,F,L,M,O,P,R

X

X

X

X

X

MT-241575W-FR

#

24

15 (75 on AXIS)

D,E,F,L,M,O,P,R

X

X

X

X

*

MT-2475W-FR

24

75

D,E,F,L,M,O,P,R

X

X

X

X

*

MTWP-2475W-FR**

24

75** (@ -°31F/-35°C

M

X

X

X

X

*

MT4-115-R

115VAC

-

D,E,J,K,N,O,R

X

X

X

X

X

MT4-115-WH-VFR

##

115VAC

15

D,E,J,K,N,O,R

X

X

X

X

X

SYNC MODELS

INPUT

VOLTAGE

AVERAGE

CURRENT (AMPS)

MOUNTING

OPTIONS***

UL

MEA CSFM FM

BFP

SM-12/24-R

12 or 24

W

X

X

X

X

X

DSM-12/24-R

12 or 24

W

X

X

X

X

X

MODEL

NUMBER

AGENCY APPROVALS

MOUNTING

OPTIONS***

RATED

CANDELA

INPUT

VOLTAGE

FROM
PRECEDING
APPLIANCE,
SM,DSM,
POWER SUPPLY
OR FACP

FROM
PRECEDING
APPLIANCE,
SM,DSM,
POWER SUPPLY
OR FACP