Ordering information, Wiring diagrams – Notifier AH Series User Manual
Page 2

Page 2 of 4 — DN-5566 • 03/30/04
PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING,
SPECIFYING, OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS,
CAUTIONS, AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE
PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH
TO YOU AND/OR OTHERS.
ORDERING INFORMATION
*Refer to data sheet DN6111 for Mounting Options
NOTE: Due to continous development of our products, specifications and offerings are subject to change without
notice in accordance with Notifier’s standard terms and conditions
MODEL
INPUT
VOLTAGE
VDC
REGULATED
VOLTAGE
RANGE
VDC/FWR
STROBE
CANDELA
(cd)
AS-24MCW
24
16.0 - 33.0
15/30/75/110
AS-241575W
24
16.0 - 33.0
15 (75 on axis)
AS-121575W
12
8.0 - 17.5
15 (75 on axis)
AS-24MCC
24
16.0 - 33.0
15/30/75/95
ASWP-2475W
24
16.0 - 33.0
75 @ -31°F
TABLE 1: RATINGS PER UL 1971
DESCRIPTION
VOLUME
REVERBERANT
DBA PER UL
464 @ 10 FT.
ANECHOIC
DBA
@ 10 FT.
High
91
99
Medium
88
95
Low
83
90
High 87
99
Medium
84
95
Low
79
90
TABLE 2: DBA RATINGS FOR 12 VDC & 24 VDC SERIES
AS/AH 12 & 24 VDC AUDIBLE
Continuous
Horn
Code 3 Horn
UL MEA CSFM FM BFP
AS-24MCW-FR
15/30/75/110
X
X
24
WALL
A,B,D,E,F,G,H,J,N,O,R,X X
X
X
X
X
AS-24MCW-FW
15/30/75/110
X
X
24
WALL
A,B,D,E,F,G,H,J,N,O,R,X X
X
X
X
X
AS-241575W-FR
15 (75 on Axis)
X
X
24
WALL
A,B,D,E,F,G,H,J,N,O,R,X X
X
X
X
AS-121575W-FR
15 (75 on Axis)
X
X
12
WALL
A,B,D,E,F,G,H,J,N,O,R,X X
X
X
X
AS-24MCC-FW
15/30/75/95
X
X
24
CEILING
A,B,D,E,F,G,H,J,N,O,R,X X
X
X
*
*
ASWP-2475W-FR
75 @ -31°F
X
X
24
WALL
I
X
X
X
X
X
AH-24-R
-
X
X
24
WALL/CEILING A,B,D,E,F,G,H,J,N,O,R,X X
X
X
X
X
AH-12-R
-
X
X
12
WALL/CEILING A,B,D,E,F,G,H,J,N,O,R,X X
X
X
X
X
AH-24WP-R
-
X
X
24
WALL/CEILING
K
X
X
X
X
X
AH-12-WP-R
-
X
X
12
WALL/CEILING
K
X
X
X
X
X
VDC
WALL/
CEILING
MOUNT
MOUNTING
OPTIONS*
AGENCY APPROVALS
MODEL
STROBE
CANDELA
NON-
SYNC
SYNC
W/SM,
DSM
NOTES:
SM Sync Module is rated for 3.0 amperes @ 24 VDC.
DSM Sync Module is rated for 3.0 amperes per circuit. The
maximum number of interconnected DSM modules is twenty
(20).
M ODEL
NUM BER
INP UT
VOLTAGE
(VDC)
AVERAGE
M EAN
CURRENT
@ 24 VDC
M OUNTING
OP TIONS
SM-12/24-R
24
.028
W
DSM-12/24-R
24
.035
W
SYNC MODELS/POWER SUPPLY
AS devices synchronized with SM Module single Class
“B” (Style Y) circuit
WITH audible silence feature.
WIRING DIAGRAMS
AS device non-synchronized.