Architects’ and Engineers’
Specifications

The chime appliances shall be Wheelock Series CH Chimes

and the chime strobe appliances shall be Wheelock Series

CH Chime Strobes or approved equals. The chime shall be

UL Listed under Standard 464 for Audible Signal Appliances

and chimes equipped with strobes shall be listed under UL

Standard 1971 for Emergency Devices for the Hearing-

Impaired. In addition, the strobes shall be certified to meet

the requirements of FCC Part 15, Class B and shall incorpo-

rate low temperature compensation to ensure the lowest pos-

sible current consumption.
All chimes shall use solid state components and shall provide

field selectable single stroke or vibrating operation with vol-

ume control and tone control. All models shall have a peak

Anechoic sound output of 83 dB at 10 feet and an adjustable

frequency range of 800 to 1200 Hz. All inputs shall employ

terminals that accept 12 AWG to 18 AWG wire sizes.
The strobe portion of the appliance shall produce a flash rate

of one flash per second over the Regulated Voltage Range

and shall incorporate a Xenon flashtube enclosed in a rug-

ged LEXAN® lens. The strobe shall be of low current design.

Where Multi-Candela Chime Strobes are specified, the

strobe intensity shall have a minimum of four field-selectable

settings and shall be rated per UL Standard 1971 at: 15/30/

75/110 cd or 135/185 cd for wall-mount models and 15/30/

75/95 cd or 115/177 cd for ceiling-mount models. The selec-

tor switch for selecting the candela shall be tamper-resistant

and not accessible from the front of the appliance. The 1575

candela strobe shall be specified when 15 candela UL Stan-

dard 1971 listing with 75 candela on-axis is required (e.g.,

ADA compliance).
When synchronization is required, the strobe portion of the

appliance shall be compatible with Wheelock SM, DSM sync

modules or the Wheelock PS-24-8MC Power Supply with

built-in Patented Sync Protocol. The strobes shall not drift out

of synchronization at any time during operation. If the sync

module or Power Supply fails to operate, (i.e., contacts

remain closed), the strobe shall revert to a non-synchronized

flash rate.
The chime and the chime strobe appliances shall be

designed for indoor surface or flush mounting. The chime

and chime strobe shall incorporate a chime mounting plate

with a grille cover which is secured with two screws for a

level, aesthetic finish and shall mount to standard electrical

hardware requiring no additional trimplate or adapter.
All chime and chime strobe appliances shall be backward

compatible.

Agency Listings and Approvals

The listings and approvals below apply to the Wheelock Series

CH Chimes and Chime Strobes. In some cases, certain mod-

ules may not be listed by certain approval agencies, or listing

may be in process. Consult factory for latest listing status.

UL Listed: file S5391.

CSFM approved: file 7125-10785:185.

FM approved.

MEA approved: file 151-92-E.

BFP approved