General specifi cations, N x g – Notifier FD Series UV/IR Flame Detector User Manual
Page 3
General Specifi cations
Standard Specifications
Operating Voltage Range
10 to 32 V
DC
Power Consumption
A Version:
Nominal 35 mA / 0.84 W | Maximum 65 mA / 1.6W (at 24 V
DC
)
Nominal 78 mA / 1.88 W | Maximum 112 mA / 2.7W (with heater)
AR Version: Nominal 52 mA / 1.25 W | Maximum 84 mA / 2.02W (at 24 V
DC
)
Nominal 98 mA / 2.35 W | Maximum 130 mA / 3.12W (with heater)
Temperature Range
Certified -40°C to +75°C (-40°F to +167°F)
Operational -50°C to +75°C (-58°F to +167°F)
Field of View
120° horizontal / 95° vertical @ 50% of maximum on axis distance
Spectral Range
UV Radiation 185 to 260 nanometres (1850 to 2600 angstroms) | IR Radiation in the 4.4 micron range
Time Delay
DIP switch selectable to 0, 3, 5, 7 seconds
Sensitivity Settings
DIP switch selectable to 8, 16, 24 or 32 counts per second
Typical Response Time
<6 seconds depending on fuel source, fire size and distance
Enclosure Material
Anodized, copper-free aluminum (optional stainless steel) factory sealed housing
Humidity Range
0 to 95% RH, non-condensing
Weight (with swivel)
2.1 kg / 4.5 lb. (stainless steel option 3.4 kg / 7.5 lb.)
Outputs
A Version:
0 to 20 mA - Into a maximum loop impedance of 800 Ohms at 32 V dc or 150 Ohms at 11.0 V
DC
Non-isolated loop supply
AR Version: Form C contacts rated 1 Amp at 30 V
DC
, 0.5 Amp at 125 V
AC
Selectable
energized/de-energized, latching/non-latching fire relay
Fault relay factory set as energized/non-latching, cannot be modified
Certifications
CSA and NRTL/C certified for hazardous locations. Class I, Division 1, Groups B, C and D. Temperature code T5
Enclosure type NEMA 4X, IP67. Ex d II B+H2 T5 (Class I, Zone 1, Grp II B+H2 T5)
For Canada only: CSA certified for hazardous locations. Class I, Division 1, Groups B, C and D. Temperature code T5
Enclosure type NEMA 4X. Ex d II B+H2 T5. CE Ex II 2 G, Ex d II B+H2 T5
Factory Mutual (FM) flame detector performance certification FM3260
n X g
2.50”
0.25”
4.12”
2.96”
2.60”
5.89”
3/4” NPT
(63.5 mm)
(6.4 mm)
(66.0 mm)
(104.7 mm)
(149.6 mm)
(75.2 mm)
Centre Line
Yellow Dot
VI Reflector
VI Emitters
Summary of Distances
Fuel Fire
Size
Typical
Response
n-heptane
1 ft. x 1 ft.
< 11sec @ 140 ft.
gasoline
1 ft. x 1 ft.
< 6sec @ 120 ft.
methane
30 in. plume
< 6sec @ 100 ft.
Immunity False Alarm Stimuli
Stimuli Immunity
Range
Direct/indirect sunlight
Total
1500W heater
10 ft.
Halogen, incandescent light
3 ft.
Florescent light
10 ft.
Arc welding (unmodulated)
10 ft.
Lightning Total