Ordering information wiring diagrams – Notifier 5600 Series User Manual
Page 2
Page 2 of 2 — DN-6931:A1 • 2/9/10
©2010 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Made in the U.S. A.
ing to 3.5-inch (88.9 mm) octagonal, 4-inch (101.6 mm) octag-
onal, single gang, and 4-inch (101.6 mm) square backboxes
with a square-to-round plaster ring. Wiring connections shall
be made by means of SEMS screws that shall accommodate
14 – 22 AWG wire. The detector shall contain alphanumeric
markings on the exterior of the housing to identify its tempera-
ture rating and activation method. The rate-of-rise element of
combination fixed-temperature/rate-of-rise models shall be
restorable, to allow for field-testing. The detectors shall include
an external collector that shall drop upon activation to identify
the unit in alarm.
ORDERING INFORMATION
WIRING DIAGRAMS
Model*
Identification
Method on
Exterior
Circuit Temperature
Rating
Activation
UL Protected Spacing,
10’ (3.048 m) Ceiling*
5601P
None
Single
135°F (57°C) Fixed-Temperature/Rate-of-Rise
50 ft. x 50 ft. (15.24 m x 15.24 m)
5602
Lettering
Single
194°F (90°C) Fixed-Temperature/Rate-of-Rise
50 ft. x 50 ft. (15.24 m x 15.24 m)
5603
Lettering
Single
135°F (57°C) Fixed-Temperature
25 ft. x 25 ft. (7.62 m x 7.62 m)
5604
Lettering
Single
194°F (90°C) Fixed-Temperature
25 ft. x 25 ft. (7.62 m x 7.62 m)
5621
Lettering
Dual
135°F (57°C) Fixed-Temperature/Rate-of-Rise
50 ft. x 50 ft. (15.24 m x 15.24 m)
5622
Lettering
Dual
194°F (90°C) Fixed-Temperature/Rate-of-Rise
50 ft. x 50 ft. (15.24 m x 15.24 m)
5623
Lettering
Dual
135°F (57°C) Fixed-Temperature
25 ft. x 25 ft. (7.62 m x 7.62 m)
5624
Lettering
Dual
194°F (90°C) Fixed-Temperature
25 ft. x 25 ft. (7.62 m x 7.62 m)
NOTE: Refer to NFPA 72 guidelines for spacing reductions when ceiling heights exceed 10 feet (3.048 m).
*
Add an “A” to part number for ULC model
.
Single-Circuit Models
Dual-Circuit Models
6931wir1.wmf
6931wir2.wmf