Specifications, Product line information – Notifier ND-100R User Manual
Page 2
Page 2 of 4 — DN-7006 • 05/09/05
SPECIFICATIONS
ND-100
Operating voltage range: 15 to 30 VDC.
Standby current: 300 µA @ 24 VDC (one communication
every 5 seconds with LED blink enabled).
Operating temperature range: 32° to 131°F (0° to 55°C).
Operating humidity range: 10% to 93% relative humidity (non-
condensing).
Storage temperature range: –22°F to +158°F (–30°C to
+70°C).
Duct air velocity: 100 to 4,000 feet/min (0.5 to 20.32 m/s).
Shipping weight: 3.35 lbs. (1.5 kg).
Dimensions: 14.75" (37 cm) length x 5.50" (14 cm) width x
2.75" (7 cm) deep.
ND-100 accessory current loads
@ 24 VDC
PA400: refer to PA400 data sheet DN-2405.
RA400Z: 0 mA standby, 10 mA maximum in alarm.
RTS451 and RTS451KEY: 0 mA standby, 7.5 mA maximum
in alarm.
ND-100R
Operating voltage range: 20 to 30 VDC, 24 VAC/VDC, 120/
240 VAC
auxiliary power (requires a separate auxiliary source).
Standby current: 300 µA @ 24 VDC (one communication
every 5 seconds with LED blink enabled).
Operating temperature range: 32° to 131°F (0° to 55°C).
Operating humidity range: 10% to 93% relative humidity (non-
condensing).
Storage temperature range: –22°F to +158°F (–30°C to
+70°C).
Duct air velocity: 100 to 4,000 feet/min (0.5 to 20.32 m/s).
Shipping weight: 3.90 lbs. (1.8 kg).
Dimensions: 14.75" (37 cm) length x 5.50" (14 cm) width x
2.75" (7 cm) deep.
ND-100R contact ratings
Alarm auxiliary contacts* (DPDT):
• 10 A @ 30 VDC.
• 10 A @ 277 VAC (0.75 power factor).
• 240 VA @ 249 VAC (0.4 power factor).
• 1/8 HP @ 120 VAC.
• 1/4 HP @ 240 VAC.
Supervisory contact (SPST):
• 2.0 A @ 30 VDC (resistive).
*Minimum switching current for auxiliary contact must be 100 mA
DC minimum @ 5 VDC.
ND-100R accessory current loads
@ 24 VDC
PA400:
refer to PA400 data sheet DN-2405.
RA400Z: 0 mA standby, 12 mA maximum in alarm.
RTS451 and RTS451KEY: 0 mA standby, 10 mA maximum
in alarm.
See table below for ND-100R current requirements.
PRODUCT LINE INFORMATION
ND-100
Addressable low-flow duct detector housing
with photoelectric smoke detector.
ND-100R
Addressable low-flow duct detector housing
with photoelectric smoke detector with DPDT
relay.
A5053FL
Replacement photoelectric sensor board.
A5067
Replacement power board (without relay).
A5060
Replacement power board (with relay).
ST-1.5
Metal sampling tube, duct widths 1' to 2' (
see
table on page 3 for metric lengths).
ST-3
Metal sampling tube, duct widths 2' to 4'.
ST-5
Metal sampling tube, duct widths 4' to 8'.
ST-10
Metal sampling tube, duct widths 8' to 12'.
RA400Z
Remote annunciator alarm LED.
RTS451
Remote test station. Mounts in single-gang
box. Includes red alarm LED and magnet test
switch.
RTS451KEY Key-activated remote test station.
F36-09-11
Replacement filters.
M02-04-00
Replacement test magnet.
S08-39-01
Replacement photo insect screen.
P48-61-00
Replacement end cap for plastic sampling
tube.
P48-21-00
Replacement end cap for metal sampling
tube.
T80-71-00
Replacement sampling tube.
7006crnt.tbl
RA400Z
RTS451
RTS451KEY
ND-100R current requirements (using no accessories)
Power supply voltage
20 – 30 VDC
24 VAC,
50/60 Hz
120 VAC,
50/60 Hz
220/240 VAC,
50/60 Hz
Max. standby current
26 mA
65 mA RMS
44 mA RMS
25 mA RMS
Max. alarm current
87 mA
182 mA RMS
52 mA RMS
30 mA RMS
Alarm response time
3 to 10 sec.
3 to 10 sec.
3 to 10 sec.
3 to 10 sec.
Power-up time
2 sec.
2 sec.
2 sec.
2 sec.