Engineering specifications, Agency approvals and listings, Product line information – Notifier N100-ISO User Manual

Page 2: Examples of device counts

background image

Page 2 of 2 — DN-6994:B • 01/05/2012

Notifier® is a registered trademark of Honeywell International Inc.

Notifier® and FireWarden® are registered trademarks of Honeywell

International Inc.

©2012 by Honeywell International Inc. All rights reserved. Unauthorized use

of this document is strictly prohibited.

This document is not intended to be used for installation purposes.

We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements.

All specifications are subject to change without notice.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.

www.notifier.com

Made in the U.S. A.

Engineering Specifications

Fault Isolator Modules shall be provided to automatically iso-

late wire-to-wire short circuits on an SLC loop. The Fault Isola-

tor Module shall limit the number of modules or detectors that

may be rendered inoperative by a short circuit fault on the SLC

Loop. If a wire-to-wire short occurs, the Fault Isolator Module

shall automatically open-circuit (disconnect) the SLC loop.

When the short circuit condition is corrected, the Fault Isolator

Module shall automatically reconnect the isolated section of

the SLC loop. The Fault Isolator Module shall not require any

address-setting, and its operations shall be totally automatic. It

shall not be necessary to replace or reset an Fault Isolator

Module after its normal operation. The Fault Isolator Module

shall mount in a standard 4" (10.16 cm) deep electrical box, in

a surface-mounted backbox, or in the Fire Alarm Control

Panel. It shall provide a single LED which shall flash to indi-

cate that the Isolator is operational and shall illuminate steadily

to indicate that a short circuit condition has been detected and

isolated.

Agency Approvals and Listings

These listings and approvals apply to the modules specified in

this document. In some cases, certain modules or applications

may not be listed by certain approval agencies, or listing may

be in progress. Consult factory for listing details.

UL Listed: S635.

CSFM: 7300-0028:0238.

MEA: 427-91-E Vol. 9.

• FM Approved.

Product Line Information

NOTE: “A” suffix indicates ULC Listed model.

N100-ISO: Isolator module.
N100-ISOA: Same as N100-ISO with ULC Listing.
SMB500: Optional surface-mount backbox.

Examples of Device Counts

(see notes under Applications)

52
389-

201

1g.wm

f

isolator
module

or base

isolator
module

or base

detector with

standard base

module

Starts

Next Count

detector with

relay base

Counts as...

(less than 25 total)