Fdm1(a) dual monitor module, Installation, Agency listings and approvals – Notifier FZM User Manual
Page 3: Product line information
DN-6720:C • 10/06/2010 — Page 3 of 4
FDM1(A) Dual Monitor Module
The FDM-1(A) Dual Monitor Module is intended for use in intelli-
gent, two-wire systems. It provides two independent two-wire
initiating device circuits (IDCs) at two separate, consecutive
addresses. It is capable of monitoring normally open contact fire
alarm and supervisory devices; or either normally open or nor-
mally closed security devices. The module has a single panel-
controlled LED.
NOTE: The FDM-1(A) provides two Style B (Class B) IDC circuits
ONLY. Style D (Class A) IDC circuits are NOT supported in any
application.
FDM-1(A) SPECIFICATIONS
Normal operating voltage range: 15 to 32 VDC.
Maximum current draw: 6.4 mA (LED on).
Average operating current: 750 μA (LED flashing).
Maximum IDC wiring resistance: 1,500 ohms.
Maximum IDC Voltage: 11 Volts.
Maximum IDC Current: 240 μA
EOL resistance: 47K ohms.
Maximum SLC Wiring resistance: 40 Ohms.
Temperature range: 32° to 120°F (0° to 49°C).
Humidity range: 10% to 93% (non-condensing).
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
2.125" (5.398 cm) deep.
FDM-1(A) AUTOMATIC ADDRESSING
The FDM-1(A) automatically assigns itself to two addressable
points, starting with the original address. For example, if the
FDM-1(A) is set to address “26”, then it will automatically
assign itself to addresses “26” and “27”.
NOTE: “Ones” addresses on the FDM-1(A) are 0, 2, 4, 6, or 8 only.
Terminals 6 and 7 use the first address, and terminals 8 and 9 use
the second address.
Installation
FMM-1(A), FZM-1(A), and FDM-1(A) modules mount directly
to a standard 4" (10.16 cm) square, 2.125" (5.398 cm) deep,
electrical box. They may also be mounted to the SMB500 sur-
face-mount box. Mounting hardware and installation instruc-
tions are provided with each module. All wiring must conform
to applicable local codes, ordinances, and regulations. These
modules are intended for power-limited wiring only.
The FMM-101(A) module is intended to be wired and mounted
without rigid connections inside a standard electrical box. All
wiring must conform to applicable local codes, ordinances, and
regulations.
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult fac-
tory for latest listing status.
•
UL: S635
•
ULC: S635
• FM Approved
•
CSFM: 7300-0028:0219
•
MEA: 457-99-E
•
U.S. Coast Guard:
– 161.002/23/3 (AFP-200: FMM-1/-101, FZM-1)
– 161.002/42/1 (NFS-640: FMM-1/-101)
•
Lloyd’s Register:
– 03/60011/E1 (FMM-1/-101, FZM-1)
– 94/60004/E2 (AFP-200: except FDM-1)
– 02/60007 (NFS-640: FDM-1)
•
FDNY: COA #6038 (NFS2-640, NFS-320), COA# 6058
(NFS2-3030)
Product Line Information
NOTE: “A” suffix indicates ULC-listed model.
FMM-1(A): Monitor module.
FMM-101(A): Monitor module, miniature.
FZM-1(A): Monitor module, two-wire detectors.
FDM-1(A): Monitor module, dual, two independent Class B cir-
cuits.
SMB500: Optional surface-mount backbox.
NOTE: See installation instructions and refer to the SLC Wiring
Manual, PN 51253.
!
CAUTION:
Avoid duplicating addresses on the system.