Ordering information, Agency listings and approvals – Notifier FCO-851 User Manual
Page 2

Page 2 of 2 — DN-60689:B • 12/3/2012
IntelliQuad™ is a trademark and NOTIFIER®, RealTest® and FlashScan®
are registered trademarks of Honeywell International Inc.
©2012 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Made in the U.S. A.
Operating humidity range: 15% – 90% relative humidity
(noncondensing).
Operating temperature: 0°C to 38°C (32°F to 100°F).
Air velocity: 0 – 4000 ft./min. (0 to 20 m/sec.).
ELECTRICAL SPECIFICATIONS
Operating Voltage range: 15 – 32 volts VDC.
Standby current (max. avg.): 300 μA at 24 VDC (one com-
munication every 5 seconds with LED blink enabled).
Maximum Alarm Current (LED on): 7.2 mA at 24 VDC.
CO ALARM ACTIVATION LEVELS
Alarm activation levels as defined by UL Standard 2034:
Ordering Information
NOTE: “A suffix indicates ULC listed model.
FCO-851: IntelliQuad PLUS Advanced Multi-Criteria Fire/CO
Detector.
FCO-851A: IntelliQuad PLUS Advanced Multi-Criteria Fire/CO
Detector, ULC listed.
B200S: Intelligent programmable sounder base.
B200SCOA: Intelligent programmable sounder base, ULC
listed. Includes CO detector markings in English and French.
M02-04-00: Detector Test Magnet.
M02-09-00: Telescoping Test Magnet.
Agency Listings and Approvals
The listings and approvals below apply to the primary product.
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult fac-
tory for latest listing status.
•
UL: S1115 (FCO-851).
•
ULC: S1115 (FCO-851A).
•
CSFM: 7275-0028:0264.
Concentration
of CO
Maximum Alarm Time
Response
70 (+/- 5) PPM
240 min (not less than 60 min)
150 (+/- 5) PPM
50 min (not less than 10 min)
400 (+/- 10) PPM
15 min (not less than 4 min)