beautypg.com

Red Lion RLY6A User Manual

Safety summary, Rly6, 25 amp dimensions in inches (mm), General description

background image

(100)

3.94

(60)

2.36

2

1

1.73

(44)

.31 (8)

Control

4-32 VDC

MADE IN U.S.A.

RED LION CONTROLS

RLY6A000

40 Amp

Output

24-660 VAC

SOLID STATE RELAY

YORK, PA.

4

-

M3058X

(87)

3.43

3

+

3.15

(80)

INTEGRATED HEAT SINK

OPTICALLY ISOLATED

SOLID STATE SWITCHING

SINGLE PHASE OUTPUT RATING: 25 A (RLY6) or 40 A (RLY6A)

SWITCHING: 24 TO 660 VAC

CONTROL SIGNAL: 4 TO 32 VDC

ZERO VOLTAGE TURN-ON

MOUNTS ON DIN RAIL OR DIRECTLY TO PANEL

4000 VOLT ISOLATION

BUILT-IN SNUBBER

LED “ON” INDICATOR

CAGE CLAMP TERMINATIONS

SAFETY SUMMARY

All safety related regulations, local codes and instructions

that appear in the literature or on equipment must be observed

to ensure personal safety and to prevent damage to either the

instrument or equipment connected to it. If equipment is used

in a manner not specified by the manufacturer, the protection

provided by the equipment may be impaired.

Do not use this unit to directly command motors, valves, or

other actuators not equipped with safeguards. To do so, can be

potentially harmful to persons or equipment in the event of a

fault to the unit.

MODEL RLY6/RLY6A - SINGLE PHASE DIN RAIL MOUNT SOLID STATE RELAY

Bulletin No. RLY6-E
Drawing No. LP0471
Released 04/13

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

1.18

(30)

3.94

(100)

RLY60000

2

25 Amp

Output

1

48-660 VAC

M2447

B

-

4

SOLID STATE RELAY

RED LION CONTROLS

MADE IN U.S.A.

YORK, PA.

3

Control

4-28 VDC

+

(87)

3.43

.71 (18)

3.15

(80)

.26 (6)

RLY6, 25 Amp DIMENSIONS In inches (mm)

TOP VIEW

GENERAL DESCRIPTION

The RLY60000 is a solid state relay that switches load currents up to 25 A; the RLY6A000

switches load currents up to 40 A. These units feature a zero voltage turn-on detector to minimize

radiated RFI when switching. An internal snubber guards against false triggering of the output

related to high dv/dt applications. A low level DC control signal of 4 to 32 VDC is all that is needed

for the switching operation. These units, highlighted by the inverse-parallel SCR output, provide a

greatly increased operational life over mechanical relays by avoiding the usual relay contact

problems such as: arcing, bouncing, and mechanical failure.

The RLY6/RLY6A can be directly controlled by logic/SSR drive output or sourcing output of

Red Lion Controls products.

UL Recognized Component,

File #E191578

R

LR 702877

CAUTION: Risk of Danger.

Read complete instructions prior to installation

and operation of the unit.

CAUTION: Risk of electric shock.

RLY6A, 40 Amp DIMENSIONS In inches (mm)

TOP VIEW

SPECIFICATIONS

OUTPUT SPECIFICATIONS

1. OPERATING VOLTAGE RANGE: 24 to 660 VAC

2. OPERATING FREQUENCY RANGE: 47 to 63 Hz

3. MAXIMUM CONTINUOUS LOAD CURRENT:

(See Safe Operating Conditions)

RLY6: 25 A

RMS

RLY6A: 40 A

RMS

4. SURGE CURRENT:

RLY6:

Non-Repetitive 1 Cycle: 250 A

PEAK

Non-Repetitive 1 Second: 100 A

PEAK

RLY6A:

Non-Repetitive 1 Cycle: 250 A

PEAK

Non-Repetitive 1 Second: 150 A

PEAK

5. MIN. LOAD CURRENT: 100 mA

6. LEAKAGE CURRENT @ V

OUT

(Max.): 8 mA

7. OVER VOLTAGE RATING: 1400 PIV

8. VOLTAGE DROP @ I

OUT

: 1.5 VAC

9. POWER DISSIPATION AT FULL LOAD:

RLY6: 25.0 Watts

RLY6A: 48.0 Watts

This manual is related to the following products: