beautypg.com

Connections, Operation, Multiple units – Red Lion RLY5 User Manual

Page 2: Fusing, Mechanical interrupt switch, Snubbing, Surge current, Thermal rating curves

background image

FUSING

The output of the SSR Power Unit should be protected by a fast blow I

2

t fuse

(Bussman KAX-30 or equivalent). This guards against long duration surge

currents, short circuits, etc., which may damage the SSR Power Unit.

MECHANICAL INTERRUPT SWITCH

The off-state output leakage current of the power unit is 10 mA maximum.

The voltage level of the output will rise proportional to the resistance of the load

due to this leakage current. Full line voltage can be measured when the output

is connected to a high resistance load and the power unit is in the off-state.

A mechanical interrupt switch (double pole) should be placed between both

sides of the line voltage and the load. The switch should be opened when

servicing any part of the output wiring. When measuring the off-state output

voltage of the unit for correct operation, load the output of the SSR Power Unit

with a small resistance (approximately 100 ohms).

SNUBBING

The power unit has internal snubbers to guard against transients generated by

most loads. Loads with low power factors (ie. motors) may require additional

external snubbing network.

SURGE CURRENT

When the SSR Power Unit switches a load on, an in-rush (surge) current that

is higher than the continuous load current will flow. The surge current can be

estimated from the table below which outlines the ratio of surge to steady state

current for various load devices. The surge current duration must be within the

Safe Operating Area of the Peak Surge Current vs. Time Figure. Surge currents

outside the safe operating area will shorten the life of or cause permanent

damage to the power unit.

240VAC

2

1

UNIT

POWER

SSR

3

4

+

-

OP1-C

OP1-B

OP1-A

1
2
3

4
5
6

LOAD

FUSE

DOUBLE POLE

SWITCH

AC POWER

(115/230VAC

SWITCH SELECTABLE)

MAIN CONTROL

OUTPUT

(SSR DRIVE

MODULE INSTALLED)

MODEL TCU

CONTROLLER

MODULE INSTALLED)

(SSR DRIVE

OUTPUT 2

AL2/OP2-A
AL2/OP2-B
AL2/OP2-C

COOLING OPTION

SWITCH

DOUBLE POLE

FUSE

LOAD

-
+

4

3

SSR

POWER

UNIT

1

2

240VAC

SHIELD

INDIVIDUAL RELAY CONNECTIONS

CONNECTIONS

Separate power feed lines should be run to the load side of the relay. The

controller unit and the load should NEVER share the same power feed. It is

recommended to install the SSR Power Unit as close to the load as possible to

keep the power cable runs short. This will help reduce noise from radiating

into other equipment. The input control signal cable can be run over distances

in excess of 200 ft. with shielded cable from the controller to the SSR power

unit. Connect the shield to the minus “-” terminal of the control signal, on the

SSR Power Unit and at only one end.

OPERATION

The following are important aspects of operation of the SSR power unit

which must be considered. Adhering to these guidelines will ensure reliable and

trouble free operation.

THERMAL RATING CURVES

The Thermal Rating Curve will determine the maximum allowable ambient

operating temperature for the maximum continuous load current. The two

parameters must intersect in the Safe Operating Area of the graph. Operation

outside the safe operating area will shorten the life of or cause permanent

damage to the SSR Power Unit.

The ambient temperature of the

power unit should be measured

with all of the associated

equipment operating to verify

the Thermal Ratings.

Ratio

Surge Current to

Steady State Current

5
7

10

Compressors

10

Motors (motionless)

Load Device

Incandescent Bulbs (cold)
Quartz Heaters (cold)

400

300

150

0.01

0.02

0.05

0.1

0.2

0.5

1.0

2.0

5.0

10

SURGE DURATION (Seconds)

PEAK SURGE CURRENT vs. DURATION

SAFE OPERATING AREA

PEAK

SURGE

CURRENT

(AMPERES RMS)

50

40

30

20

10

0

0

12.5

25

37.5

50

62.5

75

O

O

O

O

O

O

THERMAL RATING CURVE

AMBIENT TEMPERATURE (°C)

SAFE OPERATING AREA

O

MAXIMUM

CONTINUOUS

LOAD

CURRENT

(AMPERES RMS)

CONTROLLER

MODEL TCU

MODULE INSTALLED)

(SSR DRIVE

OUTPUT

MAIN CONTROL

SWITCH SELECTABLE)

(115/230VAC

AC POWER

SWITCH

DOUBLE POLE

FUSE

LOAD

6

5

4

3

2

1

OP1-A
OP1-B
OP1-C

-
+

4

3

SSR

POWER

UNIT

1

2

MULTIPLE RELAY CONNECTION

L1

N

N

L2

2

1

UNIT

POWER

SSR

3

4

+

-

LOAD

FUSE

DOUBLE POLE

SWITCH

SWITCH

DOUBLE POLE

FUSE

LOAD

-
+

4

3

SSR

POWER

UNIT

1

2

L3

N

MULTIPLE UNITS

For increased power handling, up to four SSR Power Units may be parallel

connected, and all controlled by a single output of an SSR Drive Module

(OMD00003). The output of the SSR Power Units must NOT be parallel

connected to the same load because of unequal current sharing among the

devices. The outputs should be wired to individual heaters, but they may share

the same supply. If five or more SSR Power Units are required, a Relay Output

Module (OMD00000) may be used in conjunction with an external +12 VDC

power source (RLC Model APS01000) to switch the SSR Power Units.