Red Lion RLY5 User Manual
Model rly5 - solid state power unit, General description, Specifications
SWITCHES UP TO 45 AMPERES @ 240 VAC
LOW LEVEL DC INPUT CONTROL SIGNAL (3-32 VDC)
OPTICALLY-ISOLATED OUTPUT
ZERO VOLTAGE TURN-ON, ZERO CURRENT TURN-OFF FOR
REDUCED RFI
INTERNAL SNUBBERS TO REDUCE FALSE TRIGGERING
RELATED TO HIGH dv/dt APPLICATIONS
SUPPLIED WITH HIGH EFFICIENCY HEATSINK FOR SUPERIOR
THERMAL and SURGE CURRENT RATINGS
GENERAL DESCRIPTION
The SSR Power Unit is a solid state relay which can switch load currents up
to 45 Amperes @ 240 VAC. The unit interfaces directly with a SSR Drive
Module (OMD00003). The input and output terminals are isolated from each
other to eliminate ground loops and noise problems. The unit features a zero
voltage turn-on and a zero current turn-off detector to minimize radiated RFI
when switching. An internal snubber minimizes inrush currents and guards
against false triggering of the output; related to high dv/dt applications. A low
DC control signal of +3 to +32 VDC is all that is needed for the switching
operation. The solid state switch, highlighted by the inverse-parallel SCR
output, provides a greatly increased operational life over a mechanical relay by
avoiding the usual relay contact problems: arcing, bouncing, mechanical
failure, etc. The solid state relay is shipped mounted to the high efficiency
heatsink for immediate installation.
MODEL RLY5 - SOLID STATE POWER UNIT
SPECIFICATIONS
OUTPUT SPECIFICATIONS
1. Operating Voltage Range: 50-280 VAC RMS
2. Operating Frequency Range: 47-63 Hz
3. Maximum Continuous Load Current: See Thermal Rating Code
4. Maximum Surge Load Current: See Peak Surge Current Curve
5. Minimum Load Current: 40 mA RMS
6. Maximum Off-State Leakage Current: 10 mA RMS
7. Maximum Transient Voltage: 600 V peak
8. Maximum Output Voltage Drop: 1.6 V peak
9. Power Dissipation at Full Load: 50 Watts
10. Maximum I
2
T: 1600A
2
sec
(For Fusing Purposes, t = 8.3 msec)
11. Minimum Off-State dv/dt protection: 500 V/usec
INPUT SPECIFICATIONS
(Use with RLC SSR Drive Module, OMD00003)
1. Control Voltage Range: 3 to 32 VDC
2. Maximum Turn-on Voltage: 3 VDC
3. Minimum Turn-off Voltage: 1 VDC
4. Maximum Reverse Voltage: -32 VDC
5. Minimum Input Impedance: 1500 Ω
6. Maximum Turn-on/Turn-off time: 8.3 msec
GENERAL SPECIFICATIONS
1. Isolation (Input to Output to Base): 4000 V RMS
2. Insulation Resistance: 10 GΩ
3. Operating Temperature Range: -30° to +75°C
4. Storage Temperature Range: -40° to +120°C
Bulletin No. RLY5-C
Drawing No. LP0254
Released 06/13
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
2.62
(66.5)
4.75 (121)
4.56 (116)
CENTERS FOR #8 SCREWS
4.50
5.50
(114)
(140)
0.20 (TYP.)
(5.1)
(5.5)
0.22 (TYP.)
DIMENSIONS In inches (mm)
MODEL
DESCRIPTION
PART NUMBER
RLY5
SSR Power Unit
RLY50000
ORDERING INFORMATION
INSTALLATION
It is recommended to mount the unit outside of an enclosure in an area where
there is unrestricted air flow. The unit should always be mounted with the fins
in a vertical position to maximize heat dissipation. If mounting the unit inside
an enclosure, the internal temperature of the enclosure will normally be higher
than the surrounding area and must be accounted for. At full rated load, the unit
will dissipate 50 watts and achieve a case temperature in excess of 90°C. In all
installations, it is important to allow at least two inches around the power unit
for proper ventilation.