beautypg.com

Typical rs-422 connections, Typical rs-485 connections, Typical rs-485 to legend connection – Red Lion GCM422 User Manual

Page 4: Troubleshooting

background image

TYPICAL RS-422 CONNECTIONS

NOTES:
1. Connect shield drain wire to earth ground.
2. RS-422 polarity: Terminal “A” is negative with respect to terminal “B”

in the mark (logic 1) condition.

3. If the RS-422 receive data inputs are not connected, the 20 mA SO output

will be indeterminate. Therefore if the receive data input is not
connected, the 20 mA SI input loop on the Red Lion Controls product
must be wired for the mark condition (current flowing) and must be
disconnected from the SO output terminals on the GCM422 Module.

4. Current flowing is a stop bit (mark) and no current flowing is a start bit

(space).

FIGURE 4

TYPICAL RS-485 CONNECTIONS

Note: Connect shield drain wire to earth ground.

For RS-485 operation, place the internal jumper in the 485 position. The

transmit and receive data lines of the GCM422 module should be wired
together. The transmit disable input must be high (+ 5 VDC) in order to
transmit data from the module (Note: This input is internally pulled high).
To receive data from an RS-485 device, the transmit disable input must be
low which forces the transmit data output into a high impedance state,
effectively disconnecting it from the two-wire bus.

Current flowing is a stop bit (mark) and no current flowing is a start bit

(space).

FIGURE 5

TYPICAL RS-485 TO LEGEND CONNECTION

FIGURE 6

TROUBLESHOOTING

For further technical assistance, contact technical support at the appropriate company numbers listed.

Red Lion Controls
20 Willow Springs Circle
York PA 17402
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839

Red Lion Controls AP

31, Kaki Bukit Road 3,

#06-04/05 TechLink

Singapore 417818

Tel +65 6744-6613

Fax +65 6743-3360

Red Lion Controls BV

Basicweg 11b

NL - 3821 BR Amersfoort

Tel +31 (0) 334 723 225

Fax +31 (0) 334 893 793