WIRING
WIRING CONNECTIONS
All conductors should meet voltage and
current ratings for each terminal. Also,
cabling should conform to appropriate
standards of good installation, local codes
and regulations. When wiring the module,
use the numbers on the label to identify the
position number with the proper function.
Strip the wire, leaving approximately 1/4"
(6 mm) of bare wire exposed. Insert the
wire into the terminal, and tighten.
1
7
13
Terminals 13 to 18
Terminals 7 to 12
Terminals 1 to 6
INPUT CONNECTIONS
6
3
-TC
+TC
-TC
+TC
N/C
2
+TC
-TC
1
1
-TC
+TC
-TC
3
4
5
2
8
7
10
9
11
+TC
-TC
4
+TC
-TC
-TC
5
14
13
16
15
17
7
8
N/C
+TC
6
12
+TC
18
+
WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT
WHILE CIRCUIT IS ALIVE UNLESS AREA IS KNOW TO BE
NON-HAZARDOUS.
INPUT AND OUTPUT (I/O) WIRING MUST BE IN
ACCORDANCE WITH CLASS I, DIV. 2 WIRING METHODS
AND IN ACCORDANCE WITH THE AUTHORITY HAVING
JURISDICTION.
LEDS
STS – STATUS LED
The Status LED is a dual color LED that provides information regarding the
state of the module. This includes indication of the various stages of the start-up
routine (power-up), as well as any errors that may occur.
Startup Routine
FIRMWARE UPGRADE
The module's firmware is stored in flash memory so that software/hardware
conflicts are avoided, and so that software features may be added in the future.
During a download, Crimson compares its own library of firmware files with
those stored in the Master module. If they do not match, Crimson will download
the necessary files. The Master then checks to make sure that the I/O modules
contain the same firmware. If they contain a different revision, the Master will
automatically copy those files into the module's flash memory. During this
process, the module LEDs will flash rapidly, starting with the top row, and
progressing through the remaining rows until the process is complete.
Error States
ALM – ALARM LED
The Alarm LED indicates the presence of an input fault condition. When one
or more Input Fault Alarm bits is high, the LED turns on. The alarms may be
disabled for unused inputs.
CONFIGURATION
Programming is done via Crimson
®
software, a Windows
®
compatible
configuration interface. Please see the Crimson manual for more information.
Rapidly Flashing Red
Module is currently running the boot loader and/
or being flash upgraded by Crimson. This occurs
for four seconds during a power up.
Steady Red
Module switching to configuration.
Green
Module performing normally.
Module is controlling properly, but has lost
communication with the Master.
Green/Pulsing Red
Module not controlling, and not communicating.
Solid Red
Red Lion Controls
Headquarters
20 Willow Springs Circle
York PA 17406
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
Red Lion Controls
China
Unit 101, XinAn Plaza
Building 13, No.99 Tianzhou Road
ShangHai, P.R. China 200223
Tel +86 21 6113-3688
Fax +86 21 6113-3683
Red Lion Controls
Europe
Printerweg 10
NL - 3821 AD Amersfoort
Tel +31 (0) 334 723 225
Fax +31 (0) 334 893 793
Red Lion Controls
India
54, Vishvas Tenement
GST Road, New Ranip,
Ahmedabad-382480 Gujarat, India
Tel +91 987 954 0503
Fax +91 79 275 31 350