beautypg.com

Leds, Configuration, Ordering information – Red Lion CSDIO User Manual

Page 5: Sts – status led, Startup routine error states alm – alarm led, Firmware upgrade

background image

LEDS

STS – STATUS LED

The Status LED is a dual color LED that provides information regarding the

state of the module. This includes indication of the various stages of the start-up
routine (power-up), as well as any errors that may occur.

Startup Routine

Error States

ALM – ALARM LED

The Alarm LED indicates the presence of a fault condition.

FIRMWARE UPGRADE

The module’s firmware is stored in flash memory so that software/hardware

conflicts are avoided, and so that software features may be added in the future.

During a download, Crimson compares its own library of firmware files with

those stored in the Master module. If they do not match, Crimson will download
the necessary files. The Master then checks to make sure that the I/O modules
contain the same firmware. If they contain a different revision, the Master will
automatically copy those files into the module's flash memory. During this
process, the module LEDs will flash rapidly, starting with the top row, and
progressing through the remaining rows until the process is complete.

CONFIGURATION

Programming is done via Crimson, a Windows

®

compatible configuration

interface. Please see the Crimson manual for more information.

5

ORDERING INFORMATION

TYPE

MODEL NO.

DESCRIPTION

PART NUMBER

Master Module

CSMSTR

Modular Controller Master, Multi Comms ports and Ethernet

CSMSTRV2

Modular Controller Master with multiple protocol converter, data
logger, web server with Virtual HMI up to QVGA (320 x 240) size and
expansion slot.

CSMSTRSX

Modular Controller Master with multiple protocol converter, data
logger, web server with Virtual HMI up to VGA (640 x 480) size and
expansion slot with increased SDRAM

CSMSTRGT

Digital Modules

CSDI014

1

Eight Inputs, Six Relay Outputs

CSDIO14R

Eight Inputs, Six Solid State Outputs

CSDIO14S

Communication

Cables (10 feet)

CBL

Programming Cable for CS, G3, & Paradigm Series

CBLPROG0

Communications Cables

1

CBLxxxxx

Software

Crimson

®

Programming Software

2

SFCRM

Crimson

®

Programming Software, Manual, and Download Cable

SFCRK

Accessories

Rail Stops (Qty 2)

RSRSTP00

Replacement Base

CSBASE00

Replacement Termination Plug

CSTERM00

Note: Certain modules are not suitable for use in Hazardous locations. Check each module’s specifications prior to installation.

1

Visit www.redlion.net for a complete list of PID modules, data acquisition modules, communications drivers and cables.

2

Free at www.redlion.net

Solid Red

Module not controlling, and not communicating.

Green/Pulsing Red

Module is controlling properly, but has lost
communication with the Master.

Module performing normally.

Green

Module switching to configuration.

Steady Red

Module is currently running the boot loader and/or
being flash upgraded by Crimson. This occurs for
four seconds during a power up.

Rapidly Flashing Red