Page 3: Din rail

background image

3

HARDWARE

INSTALLATION

DIN rail should be mounted horizontally so that the unit’s ventilation holes

are vertical in relation to cabinet orientation. A minimum clearance of 1 inch
(25.4 mm) should be maintained above and below the unit in order to ensure
proper thermal regulation.

The unit shall be installed inside a UL Listed Industrial Control Panel or

similar type of enclosure. A minimum 3.2 mm distance shall be maintained
between the hazardous live parts of the equipment and accessible parts of the
fire/electrical enclosure.

Figure 1 - Attach CSMSTR Master To DIN Rail

Figure 3 - Attach Termination Plug*

* Supplied with CSMSTR Master Module.

Figure 2 - Attach Slave Bases To DIN Rail

Figure 4 - Installation Complete

2

1

ETHERNET

RS232

RS485

RS232/PG

USB/PG

STS

5

DIN RAIL

DIN RAIL

USB/PG

ETHERNET

RS232

RS485

RS232/PG

STS

POWER SUPPLY REQUIREMENTS

It is very important that the power supply is mounted correctly if the unit is

to operate reliably. Please take care to observe the following points:

– The power supply must be mounted close to the unit, with usually not more

than 6 feet (1.8 m) of cable between the supply and the master. Ideally, the
shortest length possible should be used.

– The wire used to connect the master’s power supply should be at least

22-gage wire. If a longer cable run is used, a heavier gage wire should be
used. The routing of the cable should be kept away from large contactors,
inverters, and other devices which may generate significant electrical
noise.

– A power supply with an NEC Class 2 or Limited Power Source (LPS) and

SELV rating is to be used. This type of power supply provides isolation to
accessible circuits from hazardous voltage levels generated by a mains
power supply due to single faults. SELV is an acronym for “safety extra-
low voltage.” Safety extra-low voltage circuits shall exhibit voltages safe
to touch both under normal operating conditions and after a single fault,
such as a breakdown of a layer of basic insulation or after the failure of a
single component has occurred.

Visit www.redlion.net for a complete list of our PSDR Series of Class 2

power supplies.

DIN RAIL

RS485

RS232

ETHERNET

4

RS232/PG

USB/PG

STS

3

DEPRESS

4

min. clearance

TOP

1.00"

min. clearance

1.00"

BOTTOM