Hardware, Installation, Power supply requirements – Red Lion CSMSTRV2 User Manual
Page 3: Din rail
3
HARDWARE
INSTALLATION
DIN rail should be mounted horizontally so that the unit’s ventilation holes
are vertical in relation to cabinet orientation. A minimum clearance of 1 inch
(25.4 mm) should be maintained above and below the unit in order to ensure
proper thermal regulation.
The unit shall be installed inside a UL Listed Industrial Control Panel or
similar type of enclosure. A minimum 3.2 mm distance shall be maintained
between the hazardous live parts of the equipment and accessible parts of the
fire/electrical enclosure.
Figure 1 - Attach CSMSTR Master To DIN Rail
Figure 3 - Attach Termination Plug*
* Supplied with CSMSTR Master Module.
Figure 2 - Attach Slave Bases To DIN Rail
Figure 4 - Installation Complete
2
1
ETHERNET
RS232
RS485
RS232/PG
USB/PG
STS
5
DIN RAIL
DIN RAIL
USB/PG
ETHERNET
RS232
RS485
RS232/PG
STS
POWER SUPPLY REQUIREMENTS
It is very important that the power supply is mounted correctly if the unit is
to operate reliably. Please take care to observe the following points:
– The power supply must be mounted close to the unit, with usually not more
than 6 feet (1.8 m) of cable between the supply and the master. Ideally, the
shortest length possible should be used.
– The wire used to connect the master’s power supply should be at least
22-gage wire. If a longer cable run is used, a heavier gage wire should be
used. The routing of the cable should be kept away from large contactors,
inverters, and other devices which may generate significant electrical
noise.
– A power supply with an NEC Class 2 or Limited Power Source (LPS) and
SELV rating is to be used. This type of power supply provides isolation to
accessible circuits from hazardous voltage levels generated by a mains
power supply due to single faults. SELV is an acronym for “safety extra-
low voltage.” Safety extra-low voltage circuits shall exhibit voltages safe
to touch both under normal operating conditions and after a single fault,
such as a breakdown of a layer of basic insulation or after the failure of a
single component has occurred.
Visit www.redlion.net for a complete list of our PSDR Series of Class 2
power supplies.
DIN RAIL
RS485
RS232
ETHERNET
4
RS232/PG
USB/PG
STS
3
DEPRESS
4
min. clearance
TOP
1.00"
min. clearance
1.00"
BOTTOM