SPECIFICATIONS

1. POWER: 24 VDC ± 10%

400 mA min. (1 module)
3.5 Amps max. (16 modules + Expansion Card)
Must use NEC Class 2 or Limited Power Source (LPS) rated power supply.

2. COMMUNICATIONS:

USB/PG Port: Adheres to USB specification 1.1. Device only using Type B

connection.

Serial Ports: Format and Baud Rates for each port are individually software

programmable up to 115,200 baud.

RS232/PG Port: RS232 port via RJ12
COMMS Ports: RS422/485 port via RJ45, and RS232 port via RJ12
DH485 TXEN: Transmit enable; open collector, V

OH

= 15 VDC,

V

OL

= 0.5 V @ 25 mA max.

Ethernet Port: 10 BASE-T / 100 BASE-TX

RJ45 jack is wired as a NIC (Network Interface Card).

3. LEDs:

STS – Status LED indicates condition of master.
TX/RX – Transmit/Receive LEDs show serial activity.
Ethernet – Link and activity LEDs.
CF – CompactFlash LED indicates card status and read/write activity

4. MEMORY:

On-board User Memory: 4 Mbytes of non-volatile Flash memory.
On-board SDRAM:

CSMSTRSX: 2 Mbytes
CSMSTRGT: 8 Mbytes

Memory Card: CompactFlash Type II slot for Type I and Type II cards.

5. REAL-TIME CLOCK: Typical accuracy is less than one minute per month

drift. Crimson 2.0’s SNTP facility allows synchronization with external servers.
Battery: Lithium Coin Cell. Typical lifetime of 10 years at 25 ºC.

A “Battery Low” system variable is available so that the programmer can

choose specific action(s) to occur when the battery voltage drops below
its nominal voltage.

This unit is NOT field serviceable. All work must be done by a qualified technician.

6. ENVIRONMENTAL CONDITIONS:

Operating Temperature Range: 0 to 50°C
Storage Temperature Range: -30 to +70°C
Operating and Storage Humidity: 80% max relative humidity,

non-condensing, from 0 to 50°C

Vibration According to IEC 68-2-6: Operational 10 to 150 Hz, 0.075 mm

amplitude in X, Y, Z direction for 1.5 hours, 1 g.

Shock According to IEC 68-2-27: Operational 25 g, 11 msec in 3 directions.
Altitude: Up to 2000 meters

7. CONSTRUCTION: Case body is burgundy high impact plastic and stainless

steel. For indoor use only. Installation Category II, Pollution Degree 2.

8. POWER CONNECTION: Removable wire clamp screw terminal block.

Wire Gage Capacity: 24 AWG to 12 AWG
Torque: 4.45 to 5.34 in/lb (0.5 to 0.6 N-m)

9. MOUNTING: Snaps onto standard DIN style top hat (T) profile mounting

rails according to EN50022 -35 x 7.5 and -35 x 15.

10. CERTIFICATIONS AND COMPLIANCES:

SAFETY
Check each module’s specifications to determine system compliance.
UL Listed, File #E302106, UL508, CSA 22.2 No. 14-M05 and File #E179259,

UL61010-1, CAN/CSA-C22.2 No. 61010-1; and File #E317425, ANSI/ISA
12.12.01-2007, CSA 22.2 No. 213-M1987
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards

IECEE CB Scheme Test Report #E179259-A5-CB-1

Issued by Underwriters Laboratories Inc.

IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment

for measurement, control, and laboratory use, Part 1.

ELECTROMAGNETIC COMPATIBILITY

Emissions and Immunity to EN 61326: 2006: Electrical Equipment for
Measurement, Control and Laboratory use.

Immunity to Industrial Locations:

Electrostatic discharge

EN 61000-4-2 Criterion B

4kV contact discharge
8kV air discharge

Electromagnetic RF fields

EN 61000-4-3 Criterion B

3

10V/m (80 MHz to 1 GHz)
3 V/m (1.4 GHz to 2 GHz)
1 V/m (2 GHz to 2.7 GHz)

Fast transients (burst)

EN 61000-4-4 Criterion B

power 2kV

I/O signal 1kV

I/O signal connected to power 2kV

Surge

EN 61000-4-5 Criterion B

power 1 kV L to L, 2 kV L to G

signal 1 kV

RF conducted interference

EN 61000-4-6 Criterion A

3 Vrms

Emissions:

Emissions

EN55011

Class A

Notes:
1. Criterion A: Normal operation within specified limits.
2. Criterion B: Temporary loss of performance from which the unit self-recovers.
3. The modules with analog input and/or output signals may have their signals

deviate during disturbance but self-recover when disturbance is removed.

11. WEIGHT: 15.1 oz (456.4 g)

HARDWARE

INSTALLATION

DIN rail should be mounted horizontally so that the unit’s ventilation holes

are vertical in relation to cabinet orientation. A minimum clearance of 1 inch
(25.4 mm) should be maintained above and below the unit in order to ensure
proper thermal regulation.

The unit shall be installed inside a UL Listed Industrial Control Panel or

similar type of enclosure. A minimum 3.2 mm distance shall be maintained
between the hazardous live parts of the equipment and accessible parts of the
fire/electrical enclosure.

Figure 1 - Attach CSMSTR Master To DIN Rail and Remove

Rubber End Cap

1

2

REMOVE

2

WARNING - DO NOT CONNECT OR DISCONNECT CABLES
WHILE POWER IS APPLIED UNLESS AREA IS KNOWN TO BE
NON-HAZARDOUS. USB PORT IS FOR SYSTEM SET-UP AND
DIAGNOSTICS AND IS NOT INTENDED FOR PERMANENT
CONNECTION.

WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT
EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR
AREA IS KNOWN TO BE NON-HAZARDOUS.