SPECIFICATIONS

1. POWER: 24 VDC ± 10%

450 mA min. (1 module)

3.4 Amps max. (16 modules + Expansion Card)

Must use NEC Class 2 or Limited Power Source (LPS) rated power supply.

2. COMMUNICATIONS:

USB/PG Port: Adheres to USB 2.0 specification full speed only via Type B

connection.

USB Host Port: Complies with Universal Serial Bus Specification Rev 2.0.

Support data transfers at full-speed. Hardware over current protected

(0.5 A max).

Serial Ports: Format and Baud Rates for each port are individually software

programmable. Serial ports are individually isolated.

Communication port to port

1500 VAC

Communication ports to power 1000 VDC

Communication ports to earth

1000 VDC

Note: Units dielectric withstand test per 1 minute. Communication

ports: RS232/PG, RS232 port, RS485 port, Ethernet port and option

cards.

RS232/PG Port: RS232 port via RJ12

COMMS Ports: RS422/485 port via RJ45, and RS232 port via RJ12

DH485 TXEN: Transmit enable; open collector, V

OH

= 15 VDC,

V

OL

= 0.5 V @ 25 mA max.

Ethernet Port: 10 BASE-T / 100 BASE-TX

RJ45 jack is wired as a NIC (Network Interface Card). The jack shield is

electrically connected to Earth ground, but the port is isolated.

3. LEDs:

STS – Status LED indicates condition of master.

USB HOST – HOST LED indicates port status/activity.

TX/RX – Transmit/Receive LEDs show serial activity.

Ethernet – Link and activity LEDs.

CF – CompactFlash LED indicates card status and read/write activity

4. MEMORY:

On-board User Memory: 128 Mbytes of non-volatile Flash memory.

On-board RAM: 64 Mbytes

Memory Card: CompactFlash Type II slot for Type I and Type II cards.

5. REAL-TIME CLOCK: Typical accuracy is less than one minute per month

drift. Crimson’s SNTP facility allows synchronization with external servers.

Battery: Lithium Coin Cell. Typical lifetime of 10 years at 25 ºC.

A “Battery Low” system variable is available so that the programmer can

choose specific action(s) to occur when the battery voltage drops below

its nominal voltage.

This unit is NOT field serviceable. All work must be done by a qualified technician.

6. ENVIRONMENTAL CONDITIONS:

Operating Temperature Range: 0 to 45°C

Storage Temperature Range: -30 to +70°C

Vibration to IEC 68-2-6: Operational 5-150 Hz, 1 g

Shock to IEC 68-2-27: Operational 25 g (10 g relay)

Operating and Storage Humidity: 80% max relative humidity,

non-condensing, from 0 to 50°C

Altitude: Up to 2000 meters

7. CONSTRUCTION: Case body is burgundy high impact plastic and stainless

steel. For indoor use only. Installation Category II, Pollution Degree 2.

8. POWER CONNECTION: Removable wire clamp screw terminal block.

Wire Gage Capacity: 24 AWG to 12 AWG

Torque: 4.45 to 5.34 in/lb (0.5 to 0.6 N-m)

9. MOUNTING: Snaps onto standard DIN style top hat (T) profile mounting

rails according to EN50022 -35 x 7.5 and -35 x 15.

10. CERTIFICATIONS AND COMPLIANCES:

CE Approved

EN 61326-1 Immunity to Industrial Locations

Emission CISPR 11 Class A

Safety requirements for electrical equipment for measurement, control, and

laboratory use:

EN 61010-1: General Requirements

EN 61010-2-030: Particular Requirements for Testing and Measuring

Circuits

EN 61010-2-201: Particular Requirements for Control Equipment

RoHS Compliant

UL Listed: File #E302106

UL Hazardous: File #E317425

Refer to EMC Installation Guidelines section of the bulletin for additional

information.

11. WEIGHT: 1.30 lb (590 g)

2

WARNING - DO NOT CONNECT OR DISCONNECT CABLES

WHILE POWER IS APPLIED UNLESS AREA IS KNOWN TO BE

NON-HAZARDOUS. USB PORT IS FOR SYSTEM SET-UP AND

DIAGNOSTICS AND IS NOT INTENDED FOR PERMANENT

CONNECTION.