TABLE 4. GAS SUPPLY LINE SIZES (IN INCHES)*

MAXIMUM CAPACITY OF PIPE IN

CUBIC FEET PER HOUR

BEFORE PLACING THE HEATER IN OPERATION, CHECK FOR GAS

LEAKAGE.

Use soap and water solution or other material acceptable for

the purpose in locating the leaks.

DO NOT USE MATCHES, CANDLES,

FLAME OR OTHER SOURCES OF IGNITION FOR THIS PURPOSE.

FIGURE 5. GAS PIPING AND SEDIMENT TRAP INSTALLATION

DISCONNECT THE HEATER AND ITS MANUAL GAS SHUTOFF VALVE

FROM THE GAS SUPPLY PIPING SYSTEM DURING ANY SUPPLY

PRESSURE TESTING EXCEEDING 1/2 PSIG (3.45 kPa). GAS SUPPLY LINE

MUST BE CAPPED WHEN DISCONNECTED FROM THE HEATER FOR TEST

PRESSURES OF 1/2 PSIG (3.45 kPa) OR LESS. THE APPLIANCE NEED

NOT BE DISCONNECTED, BUT MUST BE ISOLATED FROM THE SUPPLY

PRESSURE TEST BY CLOSING THE MANUAL GAS SHUTOFF VALVE.

PURGING

Gas line purging is required with new piping or systems in which air

has entered.

CAUTION

PURGING SHOULD BE PERFORMED BY PERSONS EXPERIENCED

IN THIS TYPE GAS SERVICE. TO AVOID RISK OF FIRE OR

EXPLOSION, PURGE DISCHARGE MUST NOT ENTER CONFINED

AREAS OR SPACES WHERE IGNITION CAN OCCUR. THE AREA

MUST BE WELL VENTILATED AND ALL SOURCES OF IGNITION

MUST BE INACTIVATED OR REMOVED.

GAS METER SIZE — NATURAL GASES ONLY

Be sure the gas meter has sufficient capacity to supply the full rated gas

input of the water heater as well as the requirements of all other gas fired

equipment supplied by the meter. If gas meter is too small, ask the gas

company to install a larger meter having adequate capacity.

GAS PRESSURE REGULATOR

The gas pressure regulator is built into the gas valve and is equipped to

operate on the gas specified on model and rating plate. The regulator is

factory adjusted to deliver gas to burner at correct water column pressure

allowing for a nominal pressure drop through the controls.

The minimum gas supply pressure for input adjustment must not be less

than 6" w.c. (1.49 kPa) for natural gas and 11" w.c. (2.73 kPa).

Do not subject the combination gas valve to inlet gas pressures of more

than 14.0" w.c. (3.48 kPa) - natural gas. A service regulator is necessary

if higher gas pressures are encountered.

Gas pressure specified in Table 5, refer to flow pressure taken at pressure

tap of automatic gas valve while heater is operating.

TABLE 5.

Type of

Gas

Input

Manifold

Pressure

Natural

75,100 Btu/hr

22 KW/hr

4.0 in. W.C.

1.12 kPa

OPERATION

It is recommended that a qualified person perform the initial firing of the

heater. At this time the user should not hesitate to ask the individual any

questions which he may have in regard to the operation and maintenance

of the unit.

TO OPERATE THE HEATER

1. Close the heater drain valve (Figure 1) by turning handle

clockwise

.

2. Open a nearby hot water faucet to permit the air in the system

to escape.

3. Fully open the cold water inlet pipe valve (Figure 1) allowing the

heater and piping to be filled.

4. Close the hot water faucet as water starts to flow.
5. The heater is ready to be operated.

WARNING

DO NOT ATTEMPT TO OPERATE WATER HEATER WITH COLD

WATER INLET VALVE CLOSED.

NEVER OPERATE THE HEATER WITHOUT FIRST BEING CERTAIN

IT IS FILLED WITH WATER AND A TEMPERATURE AND PRESSURE

RELIEF VALVE IS INSTALLED IN THE RELIEF VALVE OPENING OF

THE HEATER.

LENGTH

IN

FEET

NORMAL IRON PIPE SIZES (INCHES)

INPUT IN THOUSANDS BTU/HR

1/2" 3/4" 1"

1 1/4" 1 1/2"

2"

2 1/2"

3"

4"

10

175 360 680

1400

2100 3960 6300 11000 230000

20

120 250 485

950

1460 2750 4360

7700

15800

30

97

200 375

770

1180

2200 3520

6250

12800

40

82

170 320

660

990

1900 3000

5300

10900

50

73

151 285

580

900

1680 2650

4750

9700

60

66

138 260

530

810

1520 2400

4300

8800

70

61

125 240

490

750

1400 2250

3900

8100

80

57

118 220

460

690

1300 2050

3700

7500

90

53

110 205

430

650

1220 1950

3450

7200

100

50

103 195

400

620

1150 1850

3250

6700

125

44

93

175

360

550

1020 1650

2950

6000

150

40

84

160

325

500

950

1500

2650

5500

175

37

77

145

300

460

850

1370

2450

5000

200

35

72

135

280

430

800

1280

2280

4600

LENGTH

IN

METERS

NORMAL IRON PIPE SIZES (INCHES)

INPUT IN KW

1/2" 3/4" 1"

1 1/4" 1 1/2"

2"

2 1/2"

3"

4"

3.0

51

105 199 410

615

1160 1845

3221

6735

6.1

35

73

142 278

428

805

1277

2255

4626

9.1

28

59

110 225

346

644

1031

1830

3748

12.2

24

50

94

193

290

556

878

1552

3192

15.2

21

44

83

170

264

492

776

1391

2840

18.3

19

40

76

155

237

445

703

1259

2577

21.3

18

37

70

143

220

410

659

1142

2372

24.4

17

35

64

165

202

381

600

1083

2196

27.4

16

32

60

126

190

357

571

1010

2108

30.5

15

30

57

117

182

337

542

952

1962

38.1

13

27

51

105

161

299

483

864

1757

45.7

12

25

47

95

146

278

439

776

1610

53.3

11

23

42

88

135

249

401

717

1464

61.0

10

21

40

82

126

234

375

688

1347