BLOWER MAINTENANCE

For safety and satisfactory operation it is recommended that the blower

be checked once a year by a competent service person.

1. MOTOR - The motor is factory oiled and sealed and requires no

further maintenance.

2. WHEEL - Wheel must be clean of soot, ash or any other coating

which inhibits either rotation or air flow. Remove all foreign material

from vent system.

3. The pressure switch is inside the blower control box and is connected

to the blower housing with a tube. This tubing should be soft and

pliable and show no sign of deterioration.

RELIEF VALVE

At least once a year the temperature and pressure relief valve

should be checked to ensure that it is in operating condition.

(During manual operation of this valve, avoid any contact with hot

water and take preventive steps for water damage). Lift the lever

at the top of the valve several times until the valve seats properly

and operates freely.

WARNING

THE WATER PASSING OUT OF THE VALVE DURING THIS CHECKING

OPERATION MAY BE EXTREMELY HOT. AVOID CONTACT AND

DISCHARGE SAFELY TO PREVENT WATER DAMAGE.

If the temperature and pressure relief valve on the heater discharges

periodically or continuously, a problem exists. This may be due to

unusually high water temperatures or pressures in the system, or to a

faulty relief valve. Contact your dealer or a qualified service technician

to find the cause of the problem and to correct it. This may also be due

to thermal expansion in a closed water supply system. Contact the water

supplier or local plumbing inspector on how to correct this situation.

DO

NOT PLUG THE TEMPERATURE AND PRESSURE RELIEF VALVE.

WARNING

SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO

SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE TO THE

APPLIANCE.

HOT WATER ODOR

On occasion, hot water may develop a strong odor. If this occurs drain

the heater completely, flush thoroughly, and refill. If the problem persists,

chlorination of the heater and replacement of the factory installed

magnesium anode with aluminum anode may correct the condition.

Occasionally water softener companies recommend removal of heater

anodes for odor reasons.

CAUTION

Unauthorized removal of heater anode will void the warranty. Replace

the anode as necessary to maintain corrosion protection. For further

information contact your dealer.

WINTER PROTECTION

In regions where freezing weather is encountered, all water must be

drained from unit and piping when out of service (water shut off). Drain

valve must be left open until unit is returned to service.

REPLACEMENT PARTS

Replacement parts may be ordered from the manufacturer,

authorized service agencies or distributors. When ordering parts

be sure to have the complete water heater Model Number, Serial

Number and Series Number available. This information can be

found on the rating label affixed to the water heater. Refer to the

parts list included with the water heater from the factory for more

information or call the parts department or technical support phone

number listed on the back cover of this manual for further assistance.

PREVENTIVE MAINTENANCE

RECOMMENDED PROCEDURE FOR PERIODIC

REMOVAL OF LIME DEPOSITS FROM TANK TYPE

COMMERCIAL WATER HEATERS

FIGURE 8.

The amount of calcium carbonate (lime) released from water is in direct

proportion to water temperature and usage, see chart. The higher the

water temperature or water usage, the more lime deposits are dropped

out of the water. This is the lime scale which forms in pipes, heaters

and on cooking utensils.

Lime accumulation not only reduces the life of the equipment but also

reduces efficiency of the heater and increases fuel consumption.

The usage of water softening equipment greatly reduces the hardness

of the water. However, this equipment does not always remove all of

the hardness (lime). For this reason it is recommended that a regular

schedule for deliming be maintained.

The time between cleaning will vary from weeks to months depending

upon water conditions and usage.

UN•LIME

®

and the booklet may be obtained through your dealer

or distributor.

DELIMING SOLVENTS

UN•LIME is recommended for deliming. UN•LIME is a patented food

grade acid which is safe to handle and does not create the harmful

fumes which are associated with other products.
UN•LIME may be obtained from your dealer, distributor or water heater

manufacturer. Order Part Number 9005416105, 1 gallon, packed 4

gallons per case or Part Number 9005417105, 5 gallon container.
NOTE: Un•Lime is not available for use in Canada. Hydrochloric base

acids are not recommended for use on glass-lined tanks.

CAUTION