beautypg.com

State SBB75 76NE User Manual

Page 5

background image

5

installed in a carpeted alcove or closet, the entire floor shall be covered

by the panel. Also, see the drain requirements.

THIS HEATER SHALL BE LOCATED OR PROTECTED SO IT IS

NOT SUBJECT TO PHYSICAL DAMAGE BY A MOVING VEHICLE.

WARNING

FLAMMABLE ITEMS, PRESSURIZED CONTAINERS OR ANY

OTHER POTENTIAL FIRE HAZARDOUS ARTICLES MUST

NEVER BE PLACED ON OR ADJACENT TO THE HEATER. OPEN

CONTAINERS OF FLAMMABLE MATERIAL SHOULD NOT BE

STORED OR USED IN THE SAME ROOM WITH THE HEATER.

When installing the heater, consideration must be given to proper

location. Location selected should be as close to the stack or

chimney as practicable, with adequate air supply and as centralized

with the piping system as possible.

THE HEATER MUST NOT BE LOCATED IN AN AREA WHERE IT

WILL BE SUBJECT TO FREEZING.

THE HEATER SHOULD BE LOCATED IN AN AREA WHERE

LEAKAGE FROM THE HEATER OR CONNECTIONS WILL NOT

RESULT IN DAMAGE TO THE ADJACENT AREA OR TO LOWER

FLOORS OF THE STRUCTURE.

WHEN SUCH LOCATIONS CANNOT BE AVOIDED, A SUITABLE

DRAIN PAN SHOULD BE INSTALLED UNDER THE HEATER. Such

pans should be fabricated with sides at least 2" (5cm) deep, with

length and width at least 2" (5cm) greater than the diameter of the

heater and must be piped to an adequate drain. The pan must not

restrict combustion air flow.

Drain pans suitable for these heaters are available from from the

manufacturer, authorized service agencies or distributors.

CLEARANCES

These heaters are approved for installation on combustible flooring

in a closet having a ceiling 12" (30.5cm) above top cover and with

clearances to combustible construction of 6" (15.2cm) from flue or

vent connector, 0" (0cm) at the sides and rear and 5" (10.2cm) to

front to prevent a possible fire hazard condition. A minimum of 4"

(10.2cm) shall be allowed for installation of serviceable parts.

HARD WATER

Where hard water conditions exist, water softening or the threshold

type of water treatment is recommended. This will protect

the dishwashers, coffee urns, water heaters, water piping and

other equipment.

See MAINTENANCE section for details of tank cleanout procedure.

AIR REQUIREMENTS

REFER TO CURRENT EDITION OF THE "NATIONAL FUEL GAS

CODE ANSI Z223.1/NFPA 54. FOR CANADA CONSULT CAN/

CSA-B149.1.

KEEP APPLIANCE AREA CLEAR AND FREE OF COMBUSTIBLE

MATERIALS, GASOLINE AND OTHER FLAMMABLES, VAPORS

AND LIQUIDS.

DO NOT OBSTRUCT THE FLOW OF THE COMBUSTION OR

VENTILATING AIR.

WARNING

ATTIC AND/OR EXHAUST FANS OPERATING ON THE PREMISES

WITH A WATER HEATER CAN RESULT IN CARBON MONOXIDE

POISONING AND DEATH.

OPERATION OF THESE FANS CAN PRODUCE A NEGATIVE DRAFT IN

THE AREA OF THE WATER HEATER PREVENTING THE PRODUCTS

OF COMBUSTION FROM EXHAUSTING THROUGH THE CHIMNEY

OR VENT PIPE.

The venting of the water heater should be inspected by a qualified service

technician at the time of installation and periodically thereafter to ensure

a down-draft condition does not exist.

WARNING

FOR SAFE OPERATION PROVIDE ADEQUATE AIR FOR COMBUSTION

AND VENTILATION. AN INSUFFICIENT SUPPLY OF AIR WILL CAUSE

RECIRCULATION OF COMBUSTION PRODUCTS RESULTING IN

AIR CONTAMINATION THAT MAY BE HAZARDOUS TO LIFE. SUCH

A CONDITION OFTEN WILL RESULT IN A YELLOW, LUMINOUS

BURNER FLAME, CAUSING CARBONING OR SOOTING OF THE

COMBUSTION CHAMBER, BURNERS AND FLUE TUBES AND

CREATES A RISK OF ASPHYXIATION.

Where an exhaust fan is supplied in the same room with a heater,

sufficient openings for air must be provided in the walls.

UNDERSIZED

OPENINGS WILL CAUSE AIR TO BE DRAWN INTO THE ROOM

THROUGH THE CHIMNEY, CAUSING POOR COMBUSTION.

SOOTING MAY RESULT IN SERIOUS DAMAGE TO THE HEATER

AND RISK OF FIRE OR EXPLOSION.

DO NOT OBSTRUCT THE FLOW OF COMBUSTION AND VENTILATING

AIR. ADEQUATE AIR FOR COMBUSTION AND VENTILATION MUST

BE PROVIDED FOR SAFE OPERATION.

UNCONFINED SPACE

In buildings of conventional frame, brick, or stone construction,

unconfined spaces may provide adequate air for combustion, ventilation

and draft hood dilution.

If the unconfined space is within a building of tight construction (buildings

using the following construction: weather stripping, heavy insulation,

caulking, vapor barrier, etc.), air for combustion, ventilation and draft hood

dilution must be obtained from outdoors. The installation instructions

for confined spaces in tightly constructed buildings must be followed to

ensure adequate air supply.

CONFINED SPACE

When drawing combustion and dilution air from inside a conventionally

constructed building to a confined space, such a space shall be provided

with two permanent openings, ONE IN OR WITHIN 12 INCHES (30.5cm)

OF THE ENCLOSURE TOP AND ONE IN OR WITHIN 12 INCHES

(30.5cm) OF THE ENCLOSURE BOTTOM. Each opening shall have

a free area of at least one square inch per 1000 Btuh (2,225mm

2

/Kw) of

the total input of all appliances in the enclosure, but not less than 100

square inches (645 square cm).

If the confined space is within a building of tight construction, air for

combustion, ventilation, and draft hood dilution must be obtained

from outdoors. When directly communicating with the outdoors or

communicating with the outdoors through vertical ducts, two permanent

openings, located in the above manner, shall be provided. Each opening

shall have a free area of not less than one square inch per 4000 Btuh

(8,900mm

2

/Kw) of the total input of all appliances in the enclosure. If

horizontal ducts are used, each opening shall have a free area of not

less than one square inch per 2000 Btuh (4,450mm

2

/Kw) of the total input

of all appliances in the enclosure. For Canadian installations consult

CAN/CSA-B149.1.