beautypg.com

State SBB75 76NE User Manual

Page 7

background image

7

THERMOMETERS (Not Supplied)

Thermometers should be obtained and field installed as shown in

Figure 3.
Thermometers are installed in the system as a means of detecting the

temperature of the outlet water supply.

COMBINATION WATER (POTABLE) HEATING

AND SPACE HEATING

1. All piping components connected to this unit for space heating

applications shall be suitable for use with potable water.

2. Toxic chemicals, such as those used for boiler treatment, shall

NEVER be introduced into this system.

3. This unit may NEVER be connected to any existing heating system

or component(s) previously used with a non-potable water heating

appliance.

4. When the system requires water for space heating at temperatures

higher than required for domestic water purposes, a tempering

valve must be installed. Please refer to installation diagram on

page 6 of this manual for suggested piping arrangements.

5. These water heaters cannot be used in space heating applications

only.

CAUTION

A closed system will exist if a check valve (without bypass), pressure

reducing valve (without bypass), or a water meter (without bypass)

is installed in the cold water line between the water heater and street

main (or well).

Excessive pressure may develop in such closed systems, causing

premature tank failure or intermittent relief valve operation. This is not a

warranty failure. An expansion tank or a similar device may be required

in the inlet supply line between the appliance and the meter or valve to

compensate for the thermal expansion of the water.

SYSTEM CONNECTIONS
The system installation must conform to these instructions and to the

local code authority having jurisdiction. Good practice requires that all

heavy piping be supported.

RELIEF VALVE

This water heater is equipped with a combination temperature-pressure

relief valve that complies with the standard for relief valves for hot water

supply systems Z21.22-CSA 4.4.

FOR SAFE OPERATION OF THE

WATER HEATER, THE RELIEF VALVE(S) MUST NOT BE REMOVED

OR PLUGGED.

ASME ratings cover pressure relief capacities. ANSI ratings cover release

rate with temperature actuation.

In addition to the appliance relief valve, each remote storage tank

which may be used in conjunction with this appliance shall also be

installed with a properly sized, rated and approved combination

temperature (ANSI) and pressure (ASME) relief valve(s). This valve

shall comply with the standard for relief valves for hot water supply

systems Z21.22-CSA 4.4.

WARNING

THE PURPOSE OF RELIEF VALVE IS TO AVOID EXCESSIVE PRESSURE

OR TEMPERATURE INTO THE STEAM RANGE, WHICH MAY CAUSE

SCALDING AT FIXTURES, TANK EXPLOSION, SYSTEM OR HEATER

DAMAGE. NO VALVE IS TO BE PLACED BETWEEN THE

RELIEF

VALVE AND TANK.

Your local code authority may have other specific relief valve

requirements.

A DRAIN LINE MUST BE CONNECTED TO THE RELIEF VALVE TO

DIRECT DISCHARGE TO A SAFE LOCATION TO AVOID SCALDING OR

WATER DAMAGE. THIS LINE MUST NOT BE REDUCED FROM THE

SIZE OF THE VALVE OUTLET AND MUST NOT CONTAIN VALVES,

RESTRICTIONS NOR SHOULD IT BE LOCATED IN FREEZING AREAS.

DO NOT THREAD OR CAP THE END OF THIS LINE. RESTRICTED OR

BLOCKED DISCHARGE WILL DEFEAT THE PURPOSE OF THE VALVE

AND IS UNSAFE. DISCHARGE LINE SHALL BE INSTALLED TO ALLOW

COMPLETE DRAINAGE OF BOTH THE VALVE AND LINE.

See SERVICE INFORMATION section for procedure and precautions.

The type, size and location of the relief valves must be in accordance

with local codes. The location of the relief valve is shown in Figure 1.

The heater has a factory installed high temperature limit switch.

GAS PIPING

Contact your local gas service company to ensure that adequate gas service

is available and to review applicable installation codes for your area.

Size the main gas line in accordance with Table 4. The figures shown

are for straight lengths of pipe at 0.5 in. W.C. pressure drop, which is

considered normal for low pressure systems. Note: Fittings such as

elbows, tees and line regulators will add to the pipe pressure drop. Also

refer to the current edition of the National Fuel Gas Code. For Canadian

installations consult Canadian Installation Code CAN/CSA-B149.1.

WARNING

The minimum gas supply pressure for input adjustment is 6.0" kPa W.C.

for natural gas (11.0" kPa W.C. for propane).

THE HEATER IS NOT INTENDED FOR OPERATION AT HIGHER THAN

14" kPa WATER COLUMN SUPPLY PRESSURE. EXPOSURE TO HIGHER

GAS SUPPLY PRESSURE MAY CAUSE DAMAGE TO THE CONTROL

WHICH COULD RESULT IN FIRE OF EXPLOSION.

If overpressure has

occurred such as through improper testing of gas lines or emergency

malfunction of the supply system, the control must be checked for safe

operation. Make sure that the outside vents on the supply regulators

and the safety vent valves are protected against blockage. These are

parts of the gas supply system not the heater. Vent blockage may occur

during ice storms.

IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING FROM

CONTAMINANTS IN THE GAS WAYS. SUCH FOULING MAY CAUSE

IMPROPER OPERATION, FIRE OR EXPLOSION.

IF COPPER SUPPLY LINES ARE USED THEY MUST BE INTERNALLY

TINNED AND CERTIFIED FOR GAS SERVICE. BEFORE ATTACHING THE

GAS LINE, BE SURE THAT ALL GAS PIPE IS CLEAN ON THE INSIDE.

TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY

LINE, A DIRT LEG (SOMETIMES CALLED SEDIMENT TRAP OR DRIP

LEG) MUST BE INCORPORATED IN THE PIPING (SEE FIG. 5). THE

DIRT LEG MUST BE READILY ACCESSIBLE AND NOT SUBJECT

TO FREEZING CONDITIONS. INSTALL IN ACCORDANCE WITH

RECOMMENDATIONS OF SERVING GAS SUPPLIERS. REFER

TO THE CURRENT EDITION OF THE NATIONAL FUEL GAS CODE.

For Canadian installations consult Canadian Installation Code CAN/

CSA-B149.1.

To prevent damage, care must be taken not to apply too much torque

when attaching gas supply pipe to gas valve inlet.

Apply joint compounds (pipe dope) sparingly and only to the male threads

of pipe joints. Do not apply compounds to the first two threads. Use

compounds resistant to the action of liquefied petroleum gases.